2001-06-06 00:00:00 | 1) PREVIOUS PLAN REVIEW COMMENTS NOT | | ADDRESSED. | | 2) NO FIRE SPRINKLER DRAWINGS OR | | HYDRAULIC CALCULATIONS PROVIDED WITH | | PLANS. | | 3) FIRE ALARM NOTES SECTION INDICATES | | CLASS B, STYLE C FIRE ALARM CIRCUITS. | | ONLY CLASS A, STYLE D CIRCUITS OR | | FULLY ADDRESSABLE FIRE ALARM SYSTEM WILL | | BE ALLOWED. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|