Plan Review Notes
Plan Review Notes For Permit 01020102
Permit Number 01020102
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-06-06 00:00:001) PREVIOUS PLAN REVIEW COMMENTS NOT
 ADDRESSED.
 2) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 3) FIRE ALARM NOTES SECTION INDICATES
 CLASS B, STYLE C FIRE ALARM CIRCUITS.
 ONLY CLASS A, STYLE D CIRCUITS OR
 FULLY ADDRESSABLE FIRE ALARM SYSTEM WILL
 BE ALLOWED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910