Date |
Text |
2001-06-05 00:00:00 | FAILED: | | 1. PLEASE PROVIDE POLLUTION PREVENTION | | PLAN. POLLUTION PREVENTION PLAN MUST BE | | INSTALLED IN THE FIELD PRIOR TO ANY | | EARTH WORKS. | | 2. PLEASE PROVIDE STORM WATER | | CALCULATION FOR OUR REVIEW IF YOU HAVE | | NOT SUBMITTED TO JOSE DEL RIO, STORM | | WATER ENGINEER AT 1000 45TH STREET WPB, | | FL 33407.SEE ATTACHED | | 3. PLEASE PROVIDE PERVIOUS & IMPERVIOUS | | CALCULATIONFOR THE SITE, SIGNED AND | | SEALED BY THE DESIGN ENGINEER.THE | | TOTAL AMOUNT MUST BE EQUAL TO 100% OF | | TOTAL SITE ACRES OR S.F. | | 4. PROVIDE H.C RAMPS FOR 5' WALK AT ALL | | ENTRANCES ALONG OLD OKEECHOBEE ROAD. | | CROSS WALKS SHOULD BE WHERE PEDESTRIANS | | CROSS. | | 5. A SEPARATE PERMIT THROUGH CITY | | ENGINEERS OFFICE FOR ALL THE WORKS | | WITHIN PUBLIC R.O.W IS REQUIRED. | | 6. A SEPARATE PERMIT THROUGH PUBLIC | | UTYLITIES ENGINEERING SERVICES | | DEPARTMENT FOR ALL THE CROSS CONNECTIONS | | IS REQUIRED. | | 7. DUMPSTER ENCLOSURES MUST HAVE A MIN. | | OF 12'-6" OPENING BETWEEN THE GATE POSTS | | PER CITY STANDARD. | | IF ANY QUESTION PLEASE CONTACT 561-659- | | 8096 EXT. 8492 MOHAMMAD R. AMINI |
|