2001-06-13 00:00:00 | PLAN REVIEW# 01020102 |
| 1801 OLD OKEECHOBEE / 1705 BLDG #1 |
| TYPE OF CON:TYPE IV / PROTECTED |
| FULLY SPRINKLERED |
| OCCUPANCY: STORAGE |
| OWN: PREMIER AIRPORT CENTER, LLP |
| |
| NOTE: THIS IS A SHELL PERMIT ONLY,THE |
| ONLY USE OF THIS BUILDING WILL BE |
| "STORAGE", AS PER IMPACT FEES THAT |
| WILL BE ASSED. UNDER THE CITYS' |
| PROPERTY FILE THIS PROPERTY WILL |
| HAVE RESTRICTIONS APPLIED FOR |
| BUSINESS LICENSES FOR STORAGE ONLY. |
| BUSINESSES THAT DO NOT REGISTER |
| WILL PAY PENALTIES FOR NO OCCUPA- |
| TIONAL LICENSE PLUS BE ASSESED |
| FOR ADDITIONAL IMPACT FEES. CITY |
| ADMINISTRATIVE CODE 104.1 A CHANGE |
| OF OCCUPANCY WILL REQUIRE A BUILD- |
| ING PERMIT, 4X FEE IS ASSOCIATED |
| WHEN NO PERMIT IS PULLED. |
| |
| 1)- FL STATE STATUTE 553/ CHAPTER 468, |
| PART XII, CHAPTER 7 OF THE CITY CODE & |
| THE SBC REQUIRE A RESIDENT INSPECTOR ON |
| SITE AND REGISTERED WITH THE ASSISTANT |
| BUILDING OFFICIAL. |
| |
| 2)- SBC 903.1 REQUIRE FIRE SPRINKLER |
| PLANS FROM THE ENGINEER SIGNED,SEALED & |
| DATED, 3 SETS OF PLANS WILL BE REQUIRED |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3)- SBC TABLE 600, SQ. FOOTAGE OF THE |
| BUILDING REQUIRES THE BUILDING TO BE |
| 1 HR. PROTECTED. |
| |
| 4)- FIRE ZONE SBC 102.2.4 ROOF COVERING |
| IN THE FIRE DISTRICT SHALL CONFORM TO |
| THE REQUIREMENTS OF A CLASS "A OR B" |
| ROOF. |
| |
| 5)- SURVEY REQUIRED, SBC 104.2.2. |
| |
| 6)- SBC 1804.2 SOIL TEST REPORT WITH THE |
| MINIMUM BEARING VALUE. |
| |
| 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| BUCK ATTACHMENT FOR ALL WINDOWS, DOORS, |
| INCLUDING OVERHEAD. |
| |
| 8)- SBC 1606.4.1 AMEND/ 1707.4.1 AMEND. |
| ALL GLAZED OPENINGS WINDOWS, DOORS, AND |
| SKYLIGHTS WILL REQUIRE PRODUCT APPROVAL |
| FOR LARGE MISSLE RESISTANCE TESTING. IF |
| THE PRODUCT HASN'T RECEIVED THIS TESTING |
| STORM SHUTTERS WILL BE REQUIRED WITH |
| PRODUCT TESTING. SEE WEST PALM BEACH |
| STORM SHUTTER POLICY FOR LARGE STRUCTURE |
| |
| 9)- ROOFING SBC 1503.1.3- INSULATION |
| FASTENING SCHEDULE, WILL REQUIRE WIND |
| LOADS WIND RESISTANCE TESTING. |
| |
| 10)- SRUCTURAL STEEL SHOP DRAWINGS ARE |
| TO BE REVIEWED BY THE ENGINEER OF RECORD |
| BEFORE SUBMITTAL OF THE BUILDING DEPART- |
| MENT. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS OR ATTACHED |
| SEPERATELY. WHEN RE-SUBITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION |
| AND REMOVE AND REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING |
| THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND, |
| WILL HELP TO EXPEDITE TO YOUR PERMIT. |