Plan Review Notes
Plan Review Notes For Permit 01020102
Permit Number 01020102
Review Stop P
Sequence Number 1
Notes
Date Text
2001-02-27 00:00:00DENIED;
  
 1.ROOF DRAINS; SHOW SQ. FT. AREA THAT
 EACH ROOF DRAIN WILL DRAIN USING 94
 SPC CHAPTER 11 AND CHART 1108.4. RAIN
 FALL IS 4.5 IN. PER. HR.IN THIS AREA,
 AND 1/2 OF THE TOTAL AREA OF THE
 PARAPET WALL MUST BE USED TO CALCULATE
 THE SIZE OF ROOF DRAINS. SHOW CALKS.
  
 2.WHERE DOES RAIN WATER FROM ROOF GO
 AFTER IT LEAVES THE BUILDING? NO STORM
 SEWER, SANITARY SEWER, OR WATER
 SERVICE IS SHOWN ON SITE PLANS.
  
 3.AREA WHERE PLUMBING MIGHT BE INSTALLED
 SHOULD HAVE 6 X 4 YEE'S INSTALLED IN
 THE BUILDING DRAIN AT TIME OF INSTALL-
 ATION. THIS INSURES THE INTEGRITY OF
 THE BUILDING DRAIN.
  
 4.ONE 3" VENT SHALL BE INSTALLED THRU
 ROOF 94 SPC SEC.904.3.1.
  
 5.WATER MAIN SHOULD HAVE FUTURE DROPS
 WITH SHUTOFF VALVES WHERE PLUMBING MAY
 BE INSTALLED.