Plan Review Notes For Permit 01020102 |
Permit Number |
01020102 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-02-27 00:00:00 | DENIED; | | | | 1.ROOF DRAINS; SHOW SQ. FT. AREA THAT | | EACH ROOF DRAIN WILL DRAIN USING 94 | | SPC CHAPTER 11 AND CHART 1108.4. RAIN | | FALL IS 4.5 IN. PER. HR.IN THIS AREA, | | AND 1/2 OF THE TOTAL AREA OF THE | | PARAPET WALL MUST BE USED TO CALCULATE | | THE SIZE OF ROOF DRAINS. SHOW CALKS. | | | | 2.WHERE DOES RAIN WATER FROM ROOF GO | | AFTER IT LEAVES THE BUILDING? NO STORM | | SEWER, SANITARY SEWER, OR WATER | | SERVICE IS SHOWN ON SITE PLANS. | | | | 3.AREA WHERE PLUMBING MIGHT BE INSTALLED | | SHOULD HAVE 6 X 4 YEE'S INSTALLED IN | | THE BUILDING DRAIN AT TIME OF INSTALL- | | ATION. THIS INSURES THE INTEGRITY OF | | THE BUILDING DRAIN. | | | | 4.ONE 3" VENT SHALL BE INSTALLED THRU | | ROOF 94 SPC SEC.904.3.1. | | | | 5.WATER MAIN SHOULD HAVE FUTURE DROPS | | WITH SHUTOFF VALVES WHERE PLUMBING MAY | | BE INSTALLED. |
|