Plan Review Notes
Plan Review Notes For Permit 01020102
Permit Number 01020102
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-02-06 00:00:001) WHAT PRODUCTS WILL BE STORED IN THE
 WAREHOUSE. WILL IT BE LIGHT HAZARD,
 ORDINARY OR HIGH HAZARD. ARE ANY RACKS
 PLANNED TO BE USED.
 2) PLEASE INDICATE ALL EXISTING FIRE
 HYDRANTS, EXISTING FIRE MAINS, NEW FIRE
 HYDRANTS AND NEW WATER MAINS.
 3) A FIRE LANE MAY BE REQUIRED FOR
 BUILDING 1 BECAUSE OF ITS HEIGHT AND
 SETBACK FROM THE ROAD.
 4) A KNOX-BOX WILL BE REQUIRED.
 5) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 6) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS AND A PERMIT PRIOR
 TO INSTALLATION. CUT SHEETS, WIRING
 DIAGRAM AND BATTERY CALCULATIONS WILL
 BE REQUIRED. THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEM ARE TO BE SUPERVISED
 BY A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 THE FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 7) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. COMPLETE FIRE SPRINKLER
 PLANS AND HYDRAULIC CALCULATIONS ARE TO
 BE SUBMITTED WITH THESE DRAWINGS BEFORE
 A BUILDING PERMIT WILL BE ISSUED.
 8) PROVIDE MORE DETAILS ON THE FIRE
 PUMP ASSEMBLY PLANNED FOR THE BUILDING.
 9) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE D
 WILL BE PERMITTED.
 10) ANY CANVAS AWNINGS ARE TO BE FIRE
 RETARDANT.
 11) ALL STAIRS TO COMPLY WITH NEW STAIRS
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 12) IS BUILDING 1 BE A SINGLE TENANT
 OR MULTIPLE TENANT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910