Plan Review Notes For Permit 01020102 |
Permit Number |
01020102 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-02-26 00:00:00 | ******************* UNSAT ************** | | | | 1)NOTE: PLEASE PROVIDE NOTE AND | | CLARIFICATION ON PLAN FOR THE REQ`MENTS | | OF 110-26. | | FUTURE FIBER OPTIC RACK BEING SHOWN IN | | THE CLEARENCE AREA FOR ELECTRCIAL | | EQUIPMENT. | | PLEASE PROVIDE NOTE ONPLAN. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANYQUESTIONS | | PLEASE CALL. | | | | DEWEYPALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|