Plan Review Notes
Plan Review Notes For Permit 01020102
Permit Number 01020102
Review Stop B
Sequence Number 1
Notes
Date Text
2001-02-12 00:00:00PERMIT # 01020102
 1805 OLD OKEECHOBEE RD. (1701)
 OCCUPANCY: WAREHOUSE
 OWN: PREMIER AIRPORT CENTER, LLP
  
 1)- THE BUILDING CODE ANALYSIS" BUILDING
 AREA STATISTICS" IS FROM THE S.F.B.C.,
 THE CITY OF W.P.B. USES THE S.B.C., 1997
 EDITION. TO DO A PLAN REVIEW UNDER THE
 STANDARD BUILDING CODE ER ARE USING THE
 FOLLOWING CRITERIA:
 OCCUPANCY: STORAGE
 TYPE OF CONS: TYPE IV
 PROTECTED: 1 HOUR
 FULLY SPRINKLERED
 ALLOW AREA : 72,000 SQ. FT.
 ACTUAL AREA : 104322 SQ. FT.
  
 TABLE 500 ALLOW AREA 72,000 SQ. FT.
 SBC 503.3 AREA INCREASE
 P= 1620 F= 1460
 F/P= .90I=90% X 24,000= 21,600
 ALLOW AREA = 72,000
 TOTAL = 93,600
 ***SOLUTION***
 DIVIED THE BUILDING WITH A 4HR FIRE WALL
 MAKING (2) BUILDINGS, EACH WILL CLEARLY
 BE UNDER THE ALLOWABLE AREA.
 2)- FL STATE STATUTE 553/ CHAPTER 468,
 PARTXII, CHAPTER 7 OF THE CITY CODE &
 THE STANDARD BUILDING CODE REQUIRE A
 RESIDENT INSPECTOR ON SITE AND REGISTER-
 ED WITH ASSISTANT BUILDING OFFICIAL DON
 NEELY.
 3)- SBC104.2.2- ADDTIONAL INFORMATION RE
 QUIRED, THIS OCCUPANCY BEING STORAGE BY
 DEFINITION WILL REQUIRE ADD. INFO. FOR
 SUBCLASSIFICATIONS, SBC 312.2
 S-1 MODERATE HAZARD STORAGE
 S-2 LOW HAZARD STORAGE
 4)- FIRE SPRINKLER PLANS TO BE ENGINEER-
 ED, SIGNED SEALED & DATED. 2 SETS REQUIR
 ED BEFOFRE THE ISSUANCE OF THE PERMIT.
 SBC 903.1.
 5)- TABLE 600, INTERIOR COLUMNS & STEEL
 SUPPORTING THE ROOF REQUIRE 1 HR.
 PROTECTION, DETAILS.
 6)- FIRE ZONE SBC 102.2.4, ROOF COVERING
 IN THEFIRE DISTRICT SHALL CONFORM TO
 THE REQUIREMENTS OF A CLASS A OR B ROOF
 COVERINGS AS DEFINED IN 1503.2.
 7)- SBC 704.2.2.2, THE USAGE OF THIS
 BUILDING, IS IT A SINGLE OR MULTIPLE
 TENANTS & OCCUPANCIES?
 8)- SBC 411.1 HIGH PILED COMBUSTIBLE
 STORAGE & HIGH RACK STORAGE SYSTEMS?
 9)- SBC 104.2.2 ADDITIONAL INFORMATION:
 IS THIS A SHELL PERMIT ONLY, THEREIS NO
 RESTROOMS?
 10)- SURVEY REQUIRED, SBC 104.2.2.
 11)- SBC 1804.2 SOILS TEST REPORT WITH
 THE MINIMUM BEARING VALUE.
 12)- SBC 1606.2.6.2- COMPONENTS & CLADD-
 ING.BUCK ATTACHMENT FOR ALL WINDOWS,
 DOORS,OVERHEAD DOORS & SKYLIGHTS.
 13)- SBC 1606.4.1 AMEND. / 1707.4.1
 AMEND. ALL GLAZED OPENINGS WINDOWS,DOORS
 & SKYLIGHTS REQUIRE PRODUCT APPROVAL FOR
 LARGE MISSLE RESISTANCE. IF THIS TEST
 WASN'T PERFORMED THEN STORM SHUTTERS
 WITH EITHER DADE COUNTY OR SBCCI TESTING
 REPORTS ARE ACCEPTED.
 14)- ROOFING SBC 1503.1.3- INSULATION/
 FASTENING SCHEDULE, WILL REQUIRE WIND-
 LOADS/ WIND RESISTANCE TESTING.
 15)- STRUCTURAL STEEL SHOP DRAWINGS ARE
 TO BE REVIEWED BY THE ENGINEER AND
 APPROVED BY THE ENGINEER OF RECORD BEFOR
 SUBMITTAL TO THE BUILDING DEPARTMENT.
 16)- SBC F102.2.6 EXTERIOR WALLS LOCATED
 WITHIN 30' OF PROPERTY LINE SHALL HAVE A
 FIRE RESISTANCE OF 2 HRS. A ASSUMED
 PROPERTY LINE WILL NEED TO BE ASSIGNED
 BETWEEN BUILDINGS.
 17)- SBC TABLE 600 EXTERIOR BEARING
 WALLS BETWEEN BUILDINGS WILL REQUIRE A
 ASSIGNED PROPERTY LINE BETWEEN BUILDINGS
 40% OPENINGS ALLOWED, SEE "KNOCK OUT
 PANELS" NOTE.
 SBC F102.2.8 FABRIC CANOPIES TO COMPLY
 WITH FLAME RESISTANT MATERIALS IN ACCORD
 ANCE WITH SBC 3103.1.
 SHEET A-12 DETAIL 7/15, THIS DETAIL IS
 DESIGNATED FOR 3 DIFFERENT DETAILS, WHEN
 IT CAN BE USED FOR ONLY ONE APPLICATION
 WHICH IS ACTUALLY A ROOF EXSPANSION
 JOINT!!!
  
 BUILDING STRUCTURAL REVIEW
 JIM WITMER
 (561) 659-8096 EX. 8412