2001-02-12 00:00:00 | PERMIT # 01020102 |
| 1805 OLD OKEECHOBEE RD. (1701) |
| OCCUPANCY: WAREHOUSE |
| OWN: PREMIER AIRPORT CENTER, LLP |
| |
| 1)- THE BUILDING CODE ANALYSIS" BUILDING |
| AREA STATISTICS" IS FROM THE S.F.B.C., |
| THE CITY OF W.P.B. USES THE S.B.C., 1997 |
| EDITION. TO DO A PLAN REVIEW UNDER THE |
| STANDARD BUILDING CODE ER ARE USING THE |
| FOLLOWING CRITERIA: |
| OCCUPANCY: STORAGE |
| TYPE OF CONS: TYPE IV |
| PROTECTED: 1 HOUR |
| FULLY SPRINKLERED |
| ALLOW AREA : 72,000 SQ. FT. |
| ACTUAL AREA : 104322 SQ. FT. |
| |
| TABLE 500 ALLOW AREA 72,000 SQ. FT. |
| SBC 503.3 AREA INCREASE |
| P= 1620 F= 1460 |
| F/P= .90I=90% X 24,000= 21,600 |
| ALLOW AREA = 72,000 |
| TOTAL = 93,600 |
| ***SOLUTION*** |
| DIVIED THE BUILDING WITH A 4HR FIRE WALL |
| MAKING (2) BUILDINGS, EACH WILL CLEARLY |
| BE UNDER THE ALLOWABLE AREA. |
| 2)- FL STATE STATUTE 553/ CHAPTER 468, |
| PARTXII, CHAPTER 7 OF THE CITY CODE & |
| THE STANDARD BUILDING CODE REQUIRE A |
| RESIDENT INSPECTOR ON SITE AND REGISTER- |
| ED WITH ASSISTANT BUILDING OFFICIAL DON |
| NEELY. |
| 3)- SBC104.2.2- ADDTIONAL INFORMATION RE |
| QUIRED, THIS OCCUPANCY BEING STORAGE BY |
| DEFINITION WILL REQUIRE ADD. INFO. FOR |
| SUBCLASSIFICATIONS, SBC 312.2 |
| S-1 MODERATE HAZARD STORAGE |
| S-2 LOW HAZARD STORAGE |
| 4)- FIRE SPRINKLER PLANS TO BE ENGINEER- |
| ED, SIGNED SEALED & DATED. 2 SETS REQUIR |
| ED BEFOFRE THE ISSUANCE OF THE PERMIT. |
| SBC 903.1. |
| 5)- TABLE 600, INTERIOR COLUMNS & STEEL |
| SUPPORTING THE ROOF REQUIRE 1 HR. |
| PROTECTION, DETAILS. |
| 6)- FIRE ZONE SBC 102.2.4, ROOF COVERING |
| IN THEFIRE DISTRICT SHALL CONFORM TO |
| THE REQUIREMENTS OF A CLASS A OR B ROOF |
| COVERINGS AS DEFINED IN 1503.2. |
| 7)- SBC 704.2.2.2, THE USAGE OF THIS |
| BUILDING, IS IT A SINGLE OR MULTIPLE |
| TENANTS & OCCUPANCIES? |
| 8)- SBC 411.1 HIGH PILED COMBUSTIBLE |
| STORAGE & HIGH RACK STORAGE SYSTEMS? |
| 9)- SBC 104.2.2 ADDITIONAL INFORMATION: |
| IS THIS A SHELL PERMIT ONLY, THEREIS NO |
| RESTROOMS? |
| 10)- SURVEY REQUIRED, SBC 104.2.2. |
| 11)- SBC 1804.2 SOILS TEST REPORT WITH |
| THE MINIMUM BEARING VALUE. |
| 12)- SBC 1606.2.6.2- COMPONENTS & CLADD- |
| ING.BUCK ATTACHMENT FOR ALL WINDOWS, |
| DOORS,OVERHEAD DOORS & SKYLIGHTS. |
| 13)- SBC 1606.4.1 AMEND. / 1707.4.1 |
| AMEND. ALL GLAZED OPENINGS WINDOWS,DOORS |
| & SKYLIGHTS REQUIRE PRODUCT APPROVAL FOR |
| LARGE MISSLE RESISTANCE. IF THIS TEST |
| WASN'T PERFORMED THEN STORM SHUTTERS |
| WITH EITHER DADE COUNTY OR SBCCI TESTING |
| REPORTS ARE ACCEPTED. |
| 14)- ROOFING SBC 1503.1.3- INSULATION/ |
| FASTENING SCHEDULE, WILL REQUIRE WIND- |
| LOADS/ WIND RESISTANCE TESTING. |
| 15)- STRUCTURAL STEEL SHOP DRAWINGS ARE |
| TO BE REVIEWED BY THE ENGINEER AND |
| APPROVED BY THE ENGINEER OF RECORD BEFOR |
| SUBMITTAL TO THE BUILDING DEPARTMENT. |
| 16)- SBC F102.2.6 EXTERIOR WALLS LOCATED |
| WITHIN 30' OF PROPERTY LINE SHALL HAVE A |
| FIRE RESISTANCE OF 2 HRS. A ASSUMED |
| PROPERTY LINE WILL NEED TO BE ASSIGNED |
| BETWEEN BUILDINGS. |
| 17)- SBC TABLE 600 EXTERIOR BEARING |
| WALLS BETWEEN BUILDINGS WILL REQUIRE A |
| ASSIGNED PROPERTY LINE BETWEEN BUILDINGS |
| 40% OPENINGS ALLOWED, SEE "KNOCK OUT |
| PANELS" NOTE. |
| SBC F102.2.8 FABRIC CANOPIES TO COMPLY |
| WITH FLAME RESISTANT MATERIALS IN ACCORD |
| ANCE WITH SBC 3103.1. |
| SHEET A-12 DETAIL 7/15, THIS DETAIL IS |
| DESIGNATED FOR 3 DIFFERENT DETAILS, WHEN |
| IT CAN BE USED FOR ONLY ONE APPLICATION |
| WHICH IS ACTUALLY A ROOF EXSPANSION |
| JOINT!!! |
| |
| BUILDING STRUCTURAL REVIEW |
| JIM WITMER |
| (561) 659-8096 EX. 8412 |