Plan Review Notes For Permit 01011330 |
Permit Number |
01011330 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-30 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE TO | | BE AT LEAST THREE FEET FROM AIR | | CONDITIONER DIFFUSERS. | | 2) SYSTEM TO BE CLASS A, STYLE D. | | 3) THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEM TO BE MONITORED BY A LICENSED UL | | LISTED CENTRAL STATION APPROVED BY THE | | FIRE RESCUE DEPARTMENT. | | 4) SYSTEM AFTER INSTALLATION IS TO BE | | TESTED WITH FIRE RESCUE PERSONNEL. | | 5) PLEASE PROVIDE HORN-STROBE DEVICES | | IN WORK BAYS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|