Plan Review Notes For Permit 01011195
Permit Number 01011195
Review Stop M
Sequence Number 2
Notes
Date Text
2001-03-02 00:00:00PROVISO:DUCT SMOKE DETECTOR MUST BE
 TESTED TO SHOW COMPPLIANCE WITH NFPA
 90A 4-4.4.4.3, FAN SHUT DOWN WITH
 NOTIFICATION TO NORMALLY OCCUPIED AREAS
 BY ALARM/STROBE.
  
 AHU-5 IN THE COPY/FILE WORKROOM (ROOM
 234), SHALL HAVE ACCESS/CLEARENCE FOR
 MAINTENANCE & SERVICE AS PER 1997 SMC
 304.2.1 & 304.2.3.