Plan Review Notes For Permit 01011195 |
Permit Number |
01011195 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-03-02 00:00:00 | PROVISO:DUCT SMOKE DETECTOR MUST BE | | TESTED TO SHOW COMPPLIANCE WITH NFPA | | 90A 4-4.4.4.3, FAN SHUT DOWN WITH | | NOTIFICATION TO NORMALLY OCCUPIED AREAS | | BY ALARM/STROBE. | | | | AHU-5 IN THE COPY/FILE WORKROOM (ROOM | | 234), SHALL HAVE ACCESS/CLEARENCE FOR | | MAINTENANCE & SERVICE AS PER 1997 SMC | | 304.2.1 & 304.2.3. |
|