Plan Review Notes For Permit 01011195 |
Permit Number |
01011195 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-29 00:00:00 | **************DENIED******************** | | 1. PROVIDE INFORMATION ON EQUIPMENT TO | | BE USED. NO AC-2 DRAWING INCLUDED AS | | CALLED FOR ON SCHEDULE OF DRAWINGS. | | 2. ALL WALLS APPEAR TO GO FLOOR TO | | CEILING. PROVIDE RETURN AIR TRANSFER | | FOR AHU,S FROM ROOMS. | | 3. PROVIDE LEGEND, PLAN SHOWS EXISTING | | CHW IS THIS CONDENSER WATER OR CHILLED | | WATER? PLAN CALLS FOR CONDENSATE DRAIN | | AND EMERGENCY PAN. PROVIDE INFORMATION | | ON SECONDARY PIPIMG OR FLOAT SWITCH. | | 4. NOTE: NO COMBUSIBLE MATERIALS IN | | RETURN AIR PLENUM ABOVE CEILING AREA. | | 5. PROVIDE INFORMATION ON FAN SHUT DOWN | | BY DUCT SMOKE DETECTOR FOR ALL | | EQUIPMENT (COMMON PLENUM). | | 6. NOTE THIS PLAN CANNOT BE CROSS | | REFERENCED TO SHELL PLAN BECAUSE THE | | INFORMATION PROVIDED ON THIS PLAN DOES | | NOT CORRESPOND TO THE INFORMATION ON THE | | SHELL PLAN. |
|