2001-01-29 00:00:00 | REVIEW DONE BY M. CARSILL UNDER PERMIT | | #0001033 AS REV. 5, NOTES TRANSFERRED | | BY P. KRAUSS. | | | | 1.WRONG LIFE SAFETY CODE REFERENCED ON | | SHEET A-001.SHOULD READ 1985 EDITION | | INSTEAD OF 1994 EDITION. | | | | 2.PROVIDE SEPARATE PLANS AND PERMIT | | FOR FIRE SPRINKLER REMODEL. | | | | 3.PROVIDE SEPARATE PLANS AND PERMIT | | FOR FIRE ALARM EQUIPMENT SHOWN ON | | DRAWINGS.SYSTEM TO BE CLASS A OR | | ADDRESSABLE.CUT SHEETS, WIRING | | DIAGRAM, FLOOR PLANS AND BATTERY | | CALCULATIONS ARE TO BE PROVIDED. | | | | 4.PLEASE CLEARLY IDENTIFY EMERGENCY | | LIGHTING LOCATIONS WITHIN TENANT SPACE. | | | | 5.PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR TENANT | | SPACE. | | | | 6.PLEASE DISPLAY LOCATIONS OF PORTABLE | | FIRE EXTINGUISHERS.PLEASEPROVIDE | | RATING FOR EXTINGUISHERS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096, EXT. 8497 | | 835-2910 |
|