Plan Review Notes
Plan Review Notes For Permit 01011195
Permit Number 01011195
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-29 00:00:00REVIEW DONE BY M. CARSILL UNDER PERMIT
 #0001033 AS REV. 5, NOTES TRANSFERRED
 BY P. KRAUSS.
  
 1.WRONG LIFE SAFETY CODE REFERENCED ON
 SHEET A-001.SHOULD READ 1985 EDITION
 INSTEAD OF 1994 EDITION.
  
 2.PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE SPRINKLER REMODEL.
  
 3.PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS.SYSTEM TO BE CLASS A OR
 ADDRESSABLE.CUT SHEETS, WIRING
 DIAGRAM, FLOOR PLANS AND BATTERY
 CALCULATIONS ARE TO BE PROVIDED.
  
 4.PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHTING LOCATIONS WITHIN TENANT SPACE.
  
 5.PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR TENANT
 SPACE.
  
 6.PLEASE DISPLAY LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.PLEASEPROVIDE
 RATING FOR EXTINGUISHERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096, EXT. 8497
 835-2910