Plan Review Notes
Plan Review Notes For Permit 01011120
Permit Number 01011120
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-29 00:00:00****************** UNSAT ***************
  
  
  
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC. DO THE FANS IN
 GUEST SUITE AND DEN HAVE LT KITS?
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 AND SHOW SIZE OF EXISITNG ELECTRCIAL
 SERVICE. 215-5 AND 220-3-C-1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372