Plan Review Notes For Permit 01011120 |
Permit Number |
01011120 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-29 00:00:00 | ****************** UNSAT *************** | | | | | | | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1. | | | | 2) PLEASE NOTE EITHER MISSING EGRESS | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | PER 210-70 OF THE NEC. DO THE FANS IN | | GUEST SUITE AND DEN HAVE LT KITS? | | | | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | AND SHOW SIZE OF EXISITNG ELECTRCIAL | | SERVICE. 215-5 AND 220-3-C-1. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT8372 |
|