Plan Review Notes For Permit 01010952 |
Permit Number |
01010952 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-23 00:00:00 | 1) NO INTERIOR FINISH INFORMATION | | COULD BE LOCATED FOR PLANS. INTERIOR | | FINISH ON WALLS AND CEILINGS IN EXITS | | TO BE CLASS A OR B. IN OFFICE AREAS, THE | | INTERIOR FINISH TO BE CLASS A,B OR C. | | 2) THE 3/4 DOORS TO BE EQUIPPED WITH | | SELF-CLOSING DEVICES. | | 3) SINCE THIS IS AN EXISTING BUILDING, | | MINIMUM HEADROOM SHALL BE SEVEN FEET | | AND ANY PROJECTION FROM THE CEILING | | SHALL BE NOT LESS THAN SIX FOOT EIGHT. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|