Plan Review Notes For Permit 01010947 |
Permit Number |
01010947 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-31 00:00:00 | ******************* UNSAT ************* | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | #`S ON PLANS, AND CORRELATE WITH PANEL | | SCHEDULES. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | E CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|