2001-01-29 00:00:00 | CONTRACTOR: GEN-X CONSTRUCTION |
| 2419 S DIXIE HWY |
| 1)- FL. ACCESIBILITY CODE 4.1.6.1(C)- |
| IF ALTERATIONS OF SINGLE ELEMEMNTS, WHEN |
| CONSIDERED TOGETHER, AMOUNT TO AN ALTER- |
| ATION OF A ROOM OR SPACE IN A BUILDING |
| OR FACILITY, THE ENTIRE SPACE SHALL BE |
| MADE ACCESIBLE. THE MENS RESTROOM DOES |
| NOT MEET THE CURENT HANDICAPPED ACCESS- |
| IBILITY CODE. |
| 2)-FL. ACCESSIBILITY CODE 4.1.6.2.2- |
| DISPROPORTIONATE COST SEE ATTACHMENT OF |
| PRIORITIES IN CHOOSING WHAT ELEMENTS |
| GIVE THE GREATEST ACCESS IN THE FOLLOW- |
| ING ORDER.20 %OF CONTTRACT VALUE IS |
| WHAT IS REQUIRED PER IMPROVEMENT. |
| 3)- FL ACC. 4.13.5 MENS RESTROOM WILL |
| REQUIRE A MINIMUM CLEAR OPENING OF 32". |
| 4)- FL ACC.4.13.6 MANEUVERING CLEARANCES |
| AT DOORWAYS, THERE ISN'T ENOUGH CLEAR |
| TURNING SPACE TO MEET THE 60" DIAMETER |
| SPHERE. |
| 5)- FL ACC 4.13.9 DOOR HARDWARE REQUIRES |
| LEVER-OPERATED MECHANISMS,PUSH-TYPE MECH |
| ANISMS AND U-SHAPED HANDLES ARE ACCEPT- |
| ABLE DESIGNS. |
| 6)- FIRE ZONE: THIS BUILDING IS LOCATED |
| IN A FIRE ZONE. F102.1 NO WOOD IS ALLOW- |
| ED INEXTERIOR WALLS (F102.1) NO WOOD |
| ALLOWED IN EXTERIOR WALLS.SEE SEC. 1/3. |
| 7)- SEC. A-3, 2/3: F105.12 WOOD VENEERS |
| DO NOT CONFORM WITH SBC 1403.6.7. |
| 8)- SBC 1606.2A VELOCITY PRESSURE FOR |
| WINDOWS NOT GIVEN. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412 |