Plan Review Notes
Plan Review Notes For Permit 01010897
Permit Number 01010897
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-29 00:00:00CONTRACTOR: GEN-X CONSTRUCTION
 2419 S DIXIE HWY
 1)- FL. ACCESIBILITY CODE 4.1.6.1(C)-
 IF ALTERATIONS OF SINGLE ELEMEMNTS, WHEN
 CONSIDERED TOGETHER, AMOUNT TO AN ALTER-
 ATION OF A ROOM OR SPACE IN A BUILDING
 OR FACILITY, THE ENTIRE SPACE SHALL BE
 MADE ACCESIBLE. THE MENS RESTROOM DOES
 NOT MEET THE CURENT HANDICAPPED ACCESS-
 IBILITY CODE.
 2)-FL. ACCESSIBILITY CODE 4.1.6.2.2-
 DISPROPORTIONATE COST SEE ATTACHMENT OF
 PRIORITIES IN CHOOSING WHAT ELEMENTS
 GIVE THE GREATEST ACCESS IN THE FOLLOW-
 ING ORDER.20 %OF CONTTRACT VALUE IS
 WHAT IS REQUIRED PER IMPROVEMENT.
 3)- FL ACC. 4.13.5 MENS RESTROOM WILL
 REQUIRE A MINIMUM CLEAR OPENING OF 32".
 4)- FL ACC.4.13.6 MANEUVERING CLEARANCES
 AT DOORWAYS, THERE ISN'T ENOUGH CLEAR
 TURNING SPACE TO MEET THE 60" DIAMETER
 SPHERE.
 5)- FL ACC 4.13.9 DOOR HARDWARE REQUIRES
 LEVER-OPERATED MECHANISMS,PUSH-TYPE MECH
 ANISMS AND U-SHAPED HANDLES ARE ACCEPT-
 ABLE DESIGNS.
 6)- FIRE ZONE: THIS BUILDING IS LOCATED
 IN A FIRE ZONE. F102.1 NO WOOD IS ALLOW-
 ED INEXTERIOR WALLS (F102.1) NO WOOD
 ALLOWED IN EXTERIOR WALLS.SEE SEC. 1/3.
 7)- SEC. A-3, 2/3: F105.12 WOOD VENEERS
 DO NOT CONFORM WITH SBC 1403.6.7.
 8)- SBC 1606.2A VELOCITY PRESSURE FOR
 WINDOWS NOT GIVEN.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412