2001-02-13 00:00:00 | CHECKLIST: |
| 1-ENERGY CALCULATIONS: |
| -PROVIDE CORRECT ADDRESS FOR EACH UNIT. |
| -PREPARER TO DATE FORM. |
| -OWNER/AGENT TO DATE FORM. |
| -COMPLETELY FILL TOP OF FORM. |
| 2-PROVIDE PRODUCT APPROVAL FOR: |
| -ENTRY "INSWING" DOOR. |
| -DOUBLE FRENCH DOORS. |
| -FRENCH DOOR WITH SIDELITES. |
| -BBQ UL LISTING AND SPECIFICATIONS. |
| 3-PROVIDE COMPLETE INFORMATION FOR STORM |
| PANELS. OR APPLY FOR SEPARATE PERMIT. |
| 4-ROOF TRUSSES: |
| -TRUSS DRAWINGS ARE REVIEWED BY WHO?. |
| REVIEW STAMP DOESN'T HAVE THE FIRM |
| NAME. |
| -CLARIFY WHY THERE ARE TWO DIFFERENT |
| SEALS ON THE ENGINEERED TRUSS DWGS. |
| SEE CHAPTER 471 FLORIDA STATUTES. |
| WHO IS THE ONE RESPONSIBLE FOR THE |
| TRUSSES DESIGN? |
| 5-PROVIDE SOIL TEST REPORT AS PER SEC. |
| 1804.2.7.2 AND TABLE 1804.2.7.3 OF |
| CITY AMENDMENTS TO SBC 1997. |
| 6-PROVIDE MANUFATURER'S CERTIFICATION |
| THAT CONCRETE BLOCK EQUIVALENT |
| THICKNESS WILL PROVIDE TWO HOUR FIRE |
| RATING ACCORDING TO ASTM C140. |
| SECTION 709.3 SBC 1997. |
| |
| NOTES: |
| -THIS CHECKLIST APPLIES TO PERMIT #S: |
| 01010780, 01010786, 01010789, 01010783 |
| AND 01010778. |
| -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 659-8096 EXT. 8232. |
| -NEED TO RECORD NOTICE OF COMMENCEMENT. |