Plan Review Notes
Plan Review Notes For Permit 01010776
Permit Number 01010776
Review Stop B
Sequence Number 1
Notes
Date Text
2001-02-13 00:00:00CHECKLIST:
 1-ENERGY CALCULATIONS:
 -PROVIDE CORRECT ADDRESS FOR EACH UNIT.
 -PREPARER TO DATE FORM.
 -OWNER/AGENT TO DATE FORM.
 -COMPLETELY FILL TOP OF FORM.
 2-PROVIDE PRODUCT APPROVAL FOR:
 -ENTRY "INSWING" DOOR.
 -DOUBLE FRENCH DOORS.
 -FRENCH DOOR WITH SIDELITES.
 -BBQ UL LISTING AND SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS. OR APPLY FOR SEPARATE PERMIT.
 4-ROOF TRUSSES:
 -TRUSS DRAWINGS ARE REVIEWED BY WHO?.
 REVIEW STAMP DOESN'T HAVE THE FIRM
 NAME.
 -CLARIFY WHY THERE ARE TWO DIFFERENT
 SEALS ON THE ENGINEERED TRUSS DWGS.
 SEE CHAPTER 471 FLORIDA STATUTES.
 WHO IS THE ONE RESPONSIBLE FOR THE
 TRUSSES DESIGN?
 5-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7.2 AND TABLE 1804.2.7.3 OF
 CITY AMENDMENTS TO SBC 1997.
 6-PROVIDE MANUFATURER'S CERTIFICATION
 THAT CONCRETE BLOCK EQUIVALENT
 THICKNESS WILL PROVIDE TWO HOUR FIRE
 RATING ACCORDING TO ASTM C140.
 SECTION 709.3 SBC 1997.
  
 NOTES:
 -THIS CHECKLIST APPLIES TO PERMIT #S:
 01010780, 01010786, 01010789, 01010783
 AND 01010778.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -NEED TO RECORD NOTICE OF COMMENCEMENT.