Plan Review Notes For Permit 01010748 |
Permit Number |
01010748 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-29 00:00:00 | 221 POTTER RD. | | O/B BENITZ, TIMOTHY | | | | BUILDING PLAN REVIEW | | 1)- ENERGY CALCS. | | 2)- DISCREPANCY, SHEET A-1 SHOWS THE | | MASTER BEDROOM WITH 3 WINDOWS VS. SHEET | | # A2 NORTH ELEVATION SHOWS A ARCHED WIN- | | DOW AND A PAIR OF FRENCH DOORS. | | SHEET S-1 DETAIL 5/S2 SHOWS 6X6 POST ON | | TOP OF THE BEAM VS. A-2 A ARCHED WINDOW | | WHICH WOULD CUT THROUGH THE BEAM AND NO | | SUPPORT FOR THE 6X6 POST NOR THE LVL. | | 3)- SHEET S-2 SEC. 6/S2 SHOWS 2X6 EXIST- | | ING ROOF RAFTERS, NO BUCKETS OR HANGERS | | ARE LISTED? THERE IS ALSO NO INFORMATION | | ON THE TIE DOWN OF THE 3 2X12 LVL BEAMS | | 4)- SAME DETAIL, THE GABLE END DETAIL IS | | MISSING INFORMATION ON THE TIE DOWN? HOW | | MUCH OVERHANG IS THERE GOING TO BE? | | SHOULD THIS BE A DROPPED GABLE? | | 5)- 1606.2.6.2: COMPONENTS & CLADDING, | | MISSING ARE THE PRODUCT APPROVAL REPORTS | | ON THE GLAZED OPENINGS, WINDOWS & DOORS | | AS WELL AS THE ROOFING MATERIAL TO BE | | USED? WE ACCEPT DADE COUNTY PRODUCT | | APPROVAL REPORTS AND SBCCI REPORTS, 2 | | COPIES WILL BE REQUIRED FOR EACH REPORT | | SUBMITTED. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX. 8412 |
|