2001-01-29 00:00:00221 POTTER RD.
 O/B BENITZ, TIMOTHY
  
 BUILDING PLAN REVIEW
 1)- ENERGY CALCS.
 2)- DISCREPANCY, SHEET A-1 SHOWS THE
 MASTER BEDROOM WITH 3 WINDOWS VS. SHEET
 # A2 NORTH ELEVATION SHOWS A ARCHED WIN-
 DOW AND A PAIR OF FRENCH DOORS.
 SHEET S-1 DETAIL 5/S2 SHOWS 6X6 POST ON
 TOP OF THE BEAM VS. A-2 A ARCHED WINDOW
 WHICH WOULD CUT THROUGH THE BEAM AND NO
 SUPPORT FOR THE 6X6 POST NOR THE LVL.
 3)- SHEET S-2 SEC. 6/S2 SHOWS 2X6 EXIST-
 ING ROOF RAFTERS, NO BUCKETS OR HANGERS
 ARE LISTED? THERE IS ALSO NO INFORMATION
 ON THE TIE DOWN OF THE 3 2X12 LVL BEAMS
 4)- SAME DETAIL, THE GABLE END DETAIL IS
 MISSING INFORMATION ON THE TIE DOWN? HOW
 MUCH OVERHANG IS THERE GOING TO BE?
 SHOULD THIS BE A DROPPED GABLE?
 5)- 1606.2.6.2: COMPONENTS & CLADDING,
 MISSING ARE THE PRODUCT APPROVAL REPORTS
 ON THE GLAZED OPENINGS, WINDOWS & DOORS
 AS WELL AS THE ROOFING MATERIAL TO BE
 USED? WE ACCEPT DADE COUNTY PRODUCT
 APPROVAL REPORTS AND SBCCI REPORTS, 2
 COPIES WILL BE REQUIRED FOR EACH REPORT
 SUBMITTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX. 8412