Plan Review Notes For Permit 01010736 |
Permit Number |
01010736 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2001-11-13 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS DO NOT | | CORRELATE WITH OTHER ELEC FOR GUESTHOUSE | | /GARAGE PLANS. | | | | 2)NOTE: PLEASE NOTE THAT GARAGE IS NOT | | SHOWN? | | | | 3)NOTE: PLEASE NOTE THAT CONDUCTOR SIZES | | DO NOT MEET 310-16. 200A DISC AND PANEL | | WITH WIRE FOR 100AMPS? 310-15. W/ #6 | | NEUTRAL. | | | | 4)NOTE: PLEASE CLARFIY SIZE OF METERCAN | | PER LOAD CALCULATIONS, LOAD SHOWN AT | | 269.9 AMPS. | | | | 5)NOTE: PLEASE SHOW MEANS OF GROUNDING | | AT DETACHED HOUSE FROM MAIN SERVICE PER | | 250-32. BLDG STEEL AND COLD WATER(IF | | METAL). | | 6)NOTE: PLEASE SHOW EQUIPMENT GROUNDING | | CONDUCTOR FROM MAIN DISCONNECTS TO PANEL | | S AT GUEST HOUSE AND MAIN HOUSE. PER | | 250-122./250-32 | | | | 7)NOTE: PLEASE INDICATE MAIN HOUSE WITH | | MAIN CIRCUIT BRKR PER 225-31 DETACHED | | FROM GARAGE/GUEST HOUSE. | | | | PLEASE MAKE THE ABOVE CORRECTIONS AND | | SUBMIT THE ABOVE INFORMATION FOR REVIEW | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | PLEASE CALL TO SET UP A MEETING IF | | NEEDED. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|