2001-11-15 00:00:00 | REVISION DENIED |
| |
| 1) PROVIDE EMERGENCY ESCAPE AND EXIT |
| OPENING IN SECOND FLOOR GUEST ROOM PER |
| 97 SBC SECTION 1005.4.1. THE MINIMUM |
| NETCLEAR OPENING AREA SHALL BE 5.7 |
| SQ.FT., THE MINIMUM NET CLEAR OPENING |
| HEIGHT OF 24" AND WIDTH OF 20" (SECT. |
| 1005.4.4) & SILL HEIGHT OF NOT MORE |
| THAN 44" |
| (SECT. 1005.4.3). |
| |
| 2) INDICATE ACCESS TO ATTIC ACCESS TO |
| COMPLY WITH 97 SBC SECT. 2309.6. |
| |
| 3)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - STORM PANELS FOR FRENCH DOORS |
| |
| 4) EXTERIOR EXITWAY STAIRS: |
| - EXTERIOR STAIRS SHALL BE SEPARATED |
| FROM THE INTERIOR OF THE BUILDING BY |
| WALLS WITH A FIRE RESISTANCE RATING OF |
| NOT LESS THAN ONE HOUR, WITH FIXED OR |
| SELF-CLOSING OPENING PROTECTIVES AS |
| REQUIRED FOR ENCLOSED STAIRS. THIS |
| PROJECTION SHALL EXTEND VERTICALLY FROM |
| THE GROUND TO A POINT 10 FT. ABOVE THE |
| TOPMOST LANDING OR THE ROOF LINE, |
| WHICH-EVER IS LOWER AND HORIZONTALLY 10 |
| FT. |
| FROM EACH SIDE OF THE STAIRWAY. |
| OPENINGSWITHIN THE 10 FT. HORIZONTAL |
| EXTENSION |
| OF THE PROTECTED WALLS BEYOND THE |
| STAIRWAY SHALL BE EQUIPPED WITH FIXED |
| 3/4- HOUR ASSEMBLIES. |
| (97 SBC SEC. 1006.2.4) THE NEW WINDOWS |
| AND DOORS AT STAIRS MUST COMPLY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |
2001-10-30 00:00:00 | ************BUILDING PROVISO************ |
| |
| 1) PROVIDE MANUFACTURES SPECIFICATIONS, |
| UL LISTING INFORMATION, STRUCTURAL |
| DRAWINGS AND ELEVATION DRAWINGS FOR |
| VENTLESS FIRE BOX PRIOR TO INSTALLATION. |
| INSTALLATION MUST COMPLY WITH CHAPTER 9 |
| OF THE 97 STANDARD MECHICAL CODE. |
| A SEPARATE GAS PERMIT WILL BE REQUIRED |
| IF USING A GAS APPLIANCE IN FIRE BOX. |
| |
| 2) PROVIDE PRODUCT APPROVALS FOR DOUBLE |
| INSWING ENTRY DOORS WITH SIDELITES, |
| PRIOR TO INSTALLATION. UNIT MUST COMPLY |
| WITH LARGE MISSLE IMPACT PROTECTION |
| REQUIREMENTS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |
| |
| REVISION WAS RESUBMITTED ON 11-8-01 FOR |
| PLBG. AND ELEC. THE ITEMS REQUESTED IN |
| ABOVE PROVISO WERE ADDRESSED. |
| RM 11-15-01 |