2001-02-27 00:00:00 | |
| *************BUILDING UNSAT************* |
| |
| SBC 104.2.2 |
| |
| 1) PROVIDE PLANS THAT HAVE RAISED SEAL |
| AND ORIGINAL SIGNATURE OF DESIGNER OF |
| RECORD. |
| |
| 2) PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| |
| 3) PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| OF CITY AMENDMENTS TO 1997 SBC. |
| |
| 4) PROVIDE 2 CURRENT COMPLETE COPIES OF |
| SBCCI OR METRO DADE PRODUCT APPROVALS |
| FOR: |
| FRONT INSWING ENTRY DOOR W/ SIDELITE |
| SLIDING GLASS DOORS |
| SH WINDOWS |
| CIRCLE TOP WINDOWS |
| |
| 5) PROVIDE FLOOD ZONE ELEVATION |
| CERTIFICATE FOR NEW CONSTRUTION WITH BFE |
| |
| 6) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 7) STRUCTUAL NOTES, LATERAL LOADS REF.94 |
| SBC ON SHT A3 94 SBC IS NOT CURRENT. |
| |
| 8) EGRESS NOTE ON SHT A4 REF. NET CLEAR |
| OPENING OF NOT LESS THAN 4 SQUARE FEET, |
| EGRESS WINDOWS MUST BE GREATER THAN 4 |
| SQUARE FEET. |
| |
| 9) STAIR DETAIL ON SHT A10 REF. 94 SBC, |
| 94 SBC US NOT CURRENT, STAIRS MUST |
| COMPLY WITH 97 SBC 1006, 1007 AND 1015. |
| PICKETS MUST BE SPACE SO THAT A 4" |
| SPHERE CANNOT PAST THROUGH ANY OPENING. |
| |
| 10) PROVIDE COMPLETE LINTEL TBL. ON SHT. |
| A12 |
| |
| 11) IDENTIFY LOCATION OF CONNECTORS |
| FROM CONNECTOR SCHEDULE TO BE USED ON |
| SHT. A12 & A13 FRAMING PLANS. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH CO.,THE PERMIT PLANS STAMPED BY |
| THEM AND THE RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. |
| |
| ANY QUESTIONS PLEASE CALL, |
| FRANK KNAPP |
| BUILDING PLAN REVIEW |
| DEPARTMENT OF CONSTRUCTION SERVICES |
| CITY OF WEST PALM BEACH |
| (561) 659-8096 EXT. 8392 |