2001-01-25 00:00:00 | ***************** UNSAT *************** |
| |
| 1)NOTE: PLEASE NOTE THAT PER F.A.C SEC. |
| 481.221 PLANS ARE TO BE SIGNED AND |
| SEALED BY THE ARCHITECT OF RECORD. |
| PLEASE NOTE THAT ALL SHEETS THAT |
| CONTAIN TITLE BLOCK. |
| |
| 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 3) PLEASE NOTE MISSING OUTLET FOR A/C |
| EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| MECHANICAL CODE. UPSTAIRS |
| |
| 4) NOTE: PLEASE SHOW GROUNDING |
| ELECTRODEGOING TO BUILDING STEEL AND |
| COLD WATER |
| PER 250-50. |
| |
| 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 6) NOTE: PLEASE SHOW ALL OUTLETS |
| SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| PROTECT--ED PER 210-8-A-6. |
| |
| 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRNET PER 110-9. |
| |
| 8)NOTE: PLEASE SHOW AND CLARIFY WHERE |
| POWER FOR NEW GARAGE IS COMING FROM??? |
| |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |