Notes |
Date |
Text |
2001-04-13 00:00:00 | PLEASE PROVIDE THE FOLLOWING | | INFORMATION WITH MECHANICAL PERMIT | | APPLICATION: | | | | O.A. CALCULATIONS AS PER ASHRAE 62-89. | | | | KEY NOTES ON DRAWING A-4 #19 & 20, | | EXHAUSET SHALL BE 10' FROM OR 24" ABOVE | | O.A. INTAKE.ONE OF THE EXHAUST OULETS | | WHEN SCALED ON PLAN IS ONLY 4' 6" FROM | | O.A. INTAKE. | | | | SUBMIT DETAIL ON CONDENSER UNIT STANDS. | | | | AHU'S WITH FAN CAPACITY GREATER THAN | | 2,00 CFM SHALL HAVE FAN SHUTDOWN BY | | DUCT SMOKE DETECTOR AS PER 1997 SMC | | 406.1 AND HAVE NOTIFICATION TO | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | | | PLEASE INDICATE ON PLAN WHERE THE | | CONDENSATE IS BEING DISPOSED. |
|