Plan Review Notes
Plan Review Notes For Permit 01010487
Permit Number 01010487
Review Stop M
Sequence Number 2
Notes
Date Text
2001-04-13 00:00:00PLEASE PROVIDE THE FOLLOWING
 INFORMATION WITH MECHANICAL PERMIT
 APPLICATION:
  
 O.A. CALCULATIONS AS PER ASHRAE 62-89.
  
 KEY NOTES ON DRAWING A-4 #19 & 20,
 EXHAUSET SHALL BE 10' FROM OR 24" ABOVE
 O.A. INTAKE.ONE OF THE EXHAUST OULETS
 WHEN SCALED ON PLAN IS ONLY 4' 6" FROM
 O.A. INTAKE.
  
 SUBMIT DETAIL ON CONDENSER UNIT STANDS.
  
 AHU'S WITH FAN CAPACITY GREATER THAN
 2,00 CFM SHALL HAVE FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR AS PER 1997 SMC
 406.1 AND HAVE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
  
 PLEASE INDICATE ON PLAN WHERE THE
 CONDENSATE IS BEING DISPOSED.