Plan Review Notes
Plan Review Notes For Permit 01010487
Permit Number 01010487
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-26 00:00:00DENIED;
  
 1.COFFEE ROOM SINKS SHALL COMPLY WITH
 FACBC 4.24.1 THRU 4.24.7.
  
 2.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC 4.1.3 (10) AND 4.15. PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING. CHECK
 CLEAR FLOOR SPACE, SECOND FLOOR
 DRINKING FOUNTAIN 30"X 48".
  
 3.P-3 (RISER DIAGRAM) HORIZONTAL DRY
 VENTS ARE NOT PERMITED. 94 SPC 914.2.
  
 4.WATER RISER DIAGRAM REQUIRED.
  
 5.PROVIDE RAIN FALL CALCULATIONS, TOTAL
 SQUIRE FOOTAGE OF ROOF AREA FOR EACH
 ROOF DRAIN AND DEGREE OF PITCH FOR
 HORIZONTAL RAIN LEADERS AND STORM
 SEWER. SPC TABLE 1108.1, 1108.2 AND
 1108.4.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377