2001-01-24 00:00:00 | 5400 EAST AV. / 01010487 |
| BUILDING PLAN REVIEW |
| 1). FL ENERGY CODE 400.ABCD.2 CODE |
| COMPLIANCE CERTIFICATION- THE BUILDINGS |
| OWNER, THE OWNER ARCHETECT, OR OTHER |
| AUTHERIZED AGENT LEGALLY DESIGNATED BY |
| THE OWNER SHALL CERTIFY TO THE BUILDING |
| OFFICIAL THAT THE BUILDING IS IN COMPLI- |
| ANCE WITH THE ENERGY EFFICIENCY CODE. A |
| SIGNATURE IS REQUIRED, HIGHLIGHTED IN |
| YELLOW HIGHLIGHTER ON ENERGY CALC. SHEET |
| 2). DISCREPANCIES: |
| A). SHEET A-4, NOTE #9 IS TO BE DELETED |
| AS PER CONVERSATION WITH ARCH. 01/24/01 |
| OR LETTER DELETING NOTE #9. |
| B). SHEET S-2 IS THE SECOND FLOOR FRAM- |
| ING PLAN, SHEET S-3 ALSO INDICATES IT IS |
| THE SECOND FLOOR FRAMING PLAN? |
| C). STRUCTURAL NOTES ON S-5 SEC.3 |
| PRECAST, PRESTRESSED CONCRETE NOTE 5.A |
| ALL PRESRESSED UNITS TO BE DESIGNED TO C |
| ONFORM TO THE LATEST REQUIREMENTS OF THE |
| STANDARD BUILDING CODE NOT THE SOUTHERN |
| STANDARD CODE. |
| 3). SBC 1606.2.6.2 COMPONENTS & CLADDING |
| A BUCK DETAIL SHOWING ATTACHMENT TO THE |
| STRUCTURE WILL BE REQUIRED. |
| 4). SBC 104.2.2. ADDITIONAL INFORMATION |
| SHEET A-15 DETAIL 3&5 SHOW A HI LEG |
| TRACK ANCHORED TO THE STRUCTURE ABOVE, |
| WHAT SIZE ANCHOR IS TO BE USED, & HOW |
| OFTEN? |
| 5).PRODUCT APPROVALS: FOR ROOFING,ALL |
| GLAZED OPENINGS,WINDOWS, DOORS & SKY- |
| LIGHRS WILL REQUIRE PRODUCT APPOVAL RE- |
| PORTS COMPLYING WITH CHAP.1606/1707 OF |
| THE S.B.C.THESE ITEMS CAN BE PROVISOED: |
| THE PRODUCT APPROVALLS WOULD REQUIRE A |
| SEPERATE SUB-PERMITS WITH THE ASSOCIATED |
| FEES. |
| |