Plan Review Notes
Plan Review Notes For Permit 01010486
Permit Number 01010486
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-03-29 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 SUBMITTAL.
 2) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 3) PLEASE INDICATE WHAT PROVISIONS ARE
 MADE FOR FIRE RESCUE ACCESS IF LOSS OF
 POWER OCCURS TO THE SECURITY GATES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910