Plan Review Notes
Plan Review Notes For Permit 01010486
Permit Number 01010486
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-30 00:00:00DENIED;
  
 1.HANDICAP RESIDENCE UNIT A-8 "TYPICAL
 ROOM PLAN", DOOR SWINGS INTO CLEAR
 FLOOR SPACE OF LAV. FACBC 4.19.3.
  
 2.HORIZONTAL RAIN WATER LEADERS AT 1/8"
 PITCH PER. FT. CAN CARRY 5350 SQ. FT.
 NOT 5400 SQ. FT.INCREASE PITCH OR PIPE
 SIZE.
  
 3.GAS PIPING. SUBMIT THE FOLLOWING
 INFORMATION; LONGEST RUN IN FEET,TYPE
 OF PIPE TO BE USED, AND SPECIFCATION
 SHEETS FOR REGULATOR.
  
 4.FLOOR DRAIN IN LAUNDRY ROOMS SHALL BE
 DEEP SEAL TRAPS OR EQUIPED WITH TRAP
 PRIMERS.
  
 5.DRINKING FOUNTAIN TO COMPLY WITH FACBC
 4.1.3(10) AND 4.15. PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 6.EWH-1 RELIEF VALVE SHALL BE PIPED TO
 THE OUTSIDE. 94 SPC 507.8.4.
  
 7.EWH-2 SHEET A-7 NOTE 8 IS NOT SHOWN ON
 WATER RISER OR FLOOR PLAN.
  
 8.ATMOSPHERIC VACUUM BREAKER REQUIRED ON
 GAS WATER HEATERS, WHERE COLD WATER
 ENTERS THE BOTTOM 1/2 OF THE HEATER.
  
 9.APPROVED MECHANICAL AIR CHAMBERS TO BE
 USED SPC 607.8.2 AND MUST BE
 ACCESSIBLE 607.8.3.
  
 10.PAGE A-17A GAS RISER DIAGRAM NOTE
 STATES 3 WATER HEATER LOCATIONS.
 WHERE IS THIRD GAS WATER HEATER?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377