2001-01-30 00:00:00 | DENIED; |
| |
| 1.HANDICAP RESIDENCE UNIT A-8 "TYPICAL |
| ROOM PLAN", DOOR SWINGS INTO CLEAR |
| FLOOR SPACE OF LAV. FACBC 4.19.3. |
| |
| 2.HORIZONTAL RAIN WATER LEADERS AT 1/8" |
| PITCH PER. FT. CAN CARRY 5350 SQ. FT. |
| NOT 5400 SQ. FT.INCREASE PITCH OR PIPE |
| SIZE. |
| |
| 3.GAS PIPING. SUBMIT THE FOLLOWING |
| INFORMATION; LONGEST RUN IN FEET,TYPE |
| OF PIPE TO BE USED, AND SPECIFCATION |
| SHEETS FOR REGULATOR. |
| |
| 4.FLOOR DRAIN IN LAUNDRY ROOMS SHALL BE |
| DEEP SEAL TRAPS OR EQUIPED WITH TRAP |
| PRIMERS. |
| |
| 5.DRINKING FOUNTAIN TO COMPLY WITH FACBC |
| 4.1.3(10) AND 4.15. PROVISIONS SHALL |
| BE MADE FOR PEOPLE WHO HAVE TROUBLE |
| BENDING OR STOOPING. |
| |
| 6.EWH-1 RELIEF VALVE SHALL BE PIPED TO |
| THE OUTSIDE. 94 SPC 507.8.4. |
| |
| 7.EWH-2 SHEET A-7 NOTE 8 IS NOT SHOWN ON |
| WATER RISER OR FLOOR PLAN. |
| |
| 8.ATMOSPHERIC VACUUM BREAKER REQUIRED ON |
| GAS WATER HEATERS, WHERE COLD WATER |
| ENTERS THE BOTTOM 1/2 OF THE HEATER. |
| |
| 9.APPROVED MECHANICAL AIR CHAMBERS TO BE |
| USED SPC 607.8.2 AND MUST BE |
| ACCESSIBLE 607.8.3. |
| |
| 10.PAGE A-17A GAS RISER DIAGRAM NOTE |
| STATES 3 WATER HEATER LOCATIONS. |
| WHERE IS THIRD GAS WATER HEATER? |
| |
| PLUMBING PLAN REVIEW BY; |
| JOHN LEECH |
| 659-8096 EXT. 8377 |