Plan Review Notes For Permit 01010486 |
Permit Number |
01010486 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-02-05 00:00:00 | ***************DENIED******************* | | 1.FIRE DAMPERS ARE NOT SHOWN AT THE | | WALL PENETRATION BETWEEN THE STORAGE | | ROOMS AND THE CORRIDORS WHERE THE | | TRANSFER DUCT AND THE SUPPLY AIR DUCT | | PENETRATE THE WALLS. SHOW LOCATION AND | | INSTALLATION DETAILS PER 1997 SMC 610.6. | | 2. OUTSIDE AIR SCHEDULE DOES NOT | | CORRESPOND TO THE ROOF TOP EQUIPMENT | | NUMBERS INDICATED IN THE EQUIPMENT | | SCHEDULE NUMBERS. CORRECT NOTES TO | | REFLECT EQUIPMENT PROVIDED. | | 3. THERE ARE TWO RTU 7 INDICATED ON | | A-18AND NO RTU- 6 ON THE A/C PLAN. | | INDICATE CORRECT UNIT NUMBERS ON PLAN. | | 4. WILL THERE BE PERSONNELL ACCESS TO | | THE HIGH ROOF OVER THE PARAPET WALL? | | 5. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | NOT SHOWN ON PLAN. ANY EQUIPMENT SERVING | | AREAS USED FOR EGRESS SHALL HAVE FAN | | SHUT DOWN BY DUCT SMOKE DETECTOR WITH | | NOTIFICATION BY BUILDING FIRE ALARM | | SYSTEM PER 1997 SMC 406.2 AND NFPA 96 | | 4-4.4 |
|