Plan Review Notes For Permit 01010486
Permit Number 01010486
Review Stop M
Sequence Number 1
Notes
Date Text
2001-02-05 00:00:00***************DENIED*******************
 1.FIRE DAMPERS ARE NOT SHOWN AT THE
 WALL PENETRATION BETWEEN THE STORAGE
 ROOMS AND THE CORRIDORS WHERE THE
 TRANSFER DUCT AND THE SUPPLY AIR DUCT
 PENETRATE THE WALLS. SHOW LOCATION AND
 INSTALLATION DETAILS PER 1997 SMC 610.6.
 2. OUTSIDE AIR SCHEDULE DOES NOT
 CORRESPOND TO THE ROOF TOP EQUIPMENT
 NUMBERS INDICATED IN THE EQUIPMENT
 SCHEDULE NUMBERS. CORRECT NOTES TO
 REFLECT EQUIPMENT PROVIDED.
 3. THERE ARE TWO RTU 7 INDICATED ON
 A-18AND NO RTU- 6 ON THE A/C PLAN.
 INDICATE CORRECT UNIT NUMBERS ON PLAN.
 4. WILL THERE BE PERSONNELL ACCESS TO
 THE HIGH ROOF OVER THE PARAPET WALL?
 5. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 NOT SHOWN ON PLAN. ANY EQUIPMENT SERVING
 AREAS USED FOR EGRESS SHALL HAVE FAN
 SHUT DOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION BY BUILDING FIRE ALARM
 SYSTEM PER 1997 SMC 406.2 AND NFPA 96
 4-4.4