Plan Review Notes
Plan Review Notes For Permit 01010486
Permit Number 01010486
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-19 00:00:001) ELEVATION DRAWINGS DID NOT DISPLAY
 BUILDING ADDRESS. BUILDING ADDRESS TO
 BE INSTALLED AND COMPLY WITH CITY CODE
 REQUIREMENTS 3343-00.
 2) AWNINGS PLANNED FOR USE ARE TO BE
 FIRE RETARDANT.
 3) PLEASE PROVIDE COMPLETE FIRE
 SPRINKLER SYSTEM DRAWINGS AND HYDRAULIC
 CALCULATIONS TO THIS OFFICE. SEPARATE
 PERMIT REQUIRED.
 4) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM DRAWINGS TO THIS OFFICE.
 CUT SHEETS, WIRING DIAGRAM, BATTERY
 CALCULATIONS, FLOOR PLANS ARE REQUIRED.
 5) THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM TO BE SUPERVISED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 6) A KNOX-BOX WILL BE REQUIRED FOR
 RAPID FIRE ACCESS.
 7) PLEASE INDICATE PROPOSED FIRE RESCUE
 ACCESS TO THE NEW RESIDENTIAL FACILITY.
 SLIDING GATES ARE SHOWN ON THE SITE
 PLAN. WHAT PROVISIONS HAVE BEEN MADE
 FOR FIRE AND PARAMEDICAL ACCESS TO THE
 BUILDING. PLEASE PROVIDE SEPARATE PLANS
 AND PERMIT FOR SECURITY GATE. IS IT
 EXPECTED FOR FIRE RESCUE VEHICLES TO
 CLEAR A FOURTEEN FOOT OPENING WHEN THE
 CODE STIPULATES OPENINGS AT TWENTY FEET
 IN CLEAR WIDTH.
 8) NO EMERGENCY LIGHT SHOWN IN DAY ROOMS
 C 10 AND C 14.
 9) PORTABLE FIRE EXTINGUISHERS WHEN
 INSTALLED, ARE TO BE EQUIPPED WITH A
 CURRENT SERVICE TAG.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910