2001-01-19 00:00:00 | 1) ELEVATION DRAWINGS DID NOT DISPLAY |
| BUILDING ADDRESS. BUILDING ADDRESS TO |
| BE INSTALLED AND COMPLY WITH CITY CODE |
| REQUIREMENTS 3343-00. |
| 2) AWNINGS PLANNED FOR USE ARE TO BE |
| FIRE RETARDANT. |
| 3) PLEASE PROVIDE COMPLETE FIRE |
| SPRINKLER SYSTEM DRAWINGS AND HYDRAULIC |
| CALCULATIONS TO THIS OFFICE. SEPARATE |
| PERMIT REQUIRED. |
| 4) PLEASE PROVIDE COMPLETE FIRE ALARM |
| SYSTEM DRAWINGS TO THIS OFFICE. |
| CUT SHEETS, WIRING DIAGRAM, BATTERY |
| CALCULATIONS, FLOOR PLANS ARE REQUIRED. |
| 5) THE FIRE SPRINKLER SYSTEM AND FIRE |
| ALARM SYSTEM TO BE SUPERVISED BY A |
| LICENSED UL LISTED CENTRAL STATION |
| APPROVED BY THE FIRE RESCUE DEPARTMENT. |
| 6) A KNOX-BOX WILL BE REQUIRED FOR |
| RAPID FIRE ACCESS. |
| 7) PLEASE INDICATE PROPOSED FIRE RESCUE |
| ACCESS TO THE NEW RESIDENTIAL FACILITY. |
| SLIDING GATES ARE SHOWN ON THE SITE |
| PLAN. WHAT PROVISIONS HAVE BEEN MADE |
| FOR FIRE AND PARAMEDICAL ACCESS TO THE |
| BUILDING. PLEASE PROVIDE SEPARATE PLANS |
| AND PERMIT FOR SECURITY GATE. IS IT |
| EXPECTED FOR FIRE RESCUE VEHICLES TO |
| CLEAR A FOURTEEN FOOT OPENING WHEN THE |
| CODE STIPULATES OPENINGS AT TWENTY FEET |
| IN CLEAR WIDTH. |
| 8) NO EMERGENCY LIGHT SHOWN IN DAY ROOMS |
| C 10 AND C 14. |
| 9) PORTABLE FIRE EXTINGUISHERS WHEN |
| INSTALLED, ARE TO BE EQUIPPED WITH A |
| CURRENT SERVICE TAG. |
| |
| CAPTAIN MIKE CARSILLO |
| 659-8096,EXT.8497 |
| 835-2910 |