Plan Review Notes
Plan Review Notes For Permit 01010422
Permit Number 01010422
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-18 00:00:001) UNDERGROUND FIRE LINE INSTALLATION
 TO COMPLY WITH NFPA 24.
 2) ENTIRE BUILDING TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THIS INCLUDES ALL
 MECHANICAL, ELECTRICAL AND SERVICE ROOMS
 ALSO ALL VERTICAL SHAFTS ARE TO BE
 FIRE SPRINKLER PROTECTED.
 3) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON SITE PLAN IS POSITIONED THAT HOSE MAY
 KINK WHEN IT IS CONNECTED. PLEASE
 ADJUST AS NECESSARY.
 4) PLEASE PROVIDE SPARE HEAD BOX AND
 WRENCH.
 5) UNDERGROUND PIPING AND FIRE SPRINKLER
 SYSTEM TO BE PRESSURE TESTED AT 200 PSI.
 FOR TWO HOURS.
 6) FIRE HYDRANT INSTALLATION TO COMPLY
 WITH CITY REQUIREMENTS.
 7) NO CUT SHEETS PROVIDED FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910