Plan Review Notes For Permit 01010422 |
Permit Number |
01010422 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-18 00:00:00 | 1) UNDERGROUND FIRE LINE INSTALLATION | | TO COMPLY WITH NFPA 24. | | 2) ENTIRE BUILDING TO BE COMPLETELY FIRE | | SPRINKLER PROTECTED. THIS INCLUDES ALL | | MECHANICAL, ELECTRICAL AND SERVICE ROOMS | | ALSO ALL VERTICAL SHAFTS ARE TO BE | | FIRE SPRINKLER PROTECTED. | | 3) THE FIRE DEPARTMENT CONNECTION SHOWN | | ON SITE PLAN IS POSITIONED THAT HOSE MAY | | KINK WHEN IT IS CONNECTED. PLEASE | | ADJUST AS NECESSARY. | | 4) PLEASE PROVIDE SPARE HEAD BOX AND | | WRENCH. | | 5) UNDERGROUND PIPING AND FIRE SPRINKLER | | SYSTEM TO BE PRESSURE TESTED AT 200 PSI. | | FOR TWO HOURS. | | 6) FIRE HYDRANT INSTALLATION TO COMPLY | | WITH CITY REQUIREMENTS. | | 7) NO CUT SHEETS PROVIDED FOR FIRE | | SPRINKLER HEADS PLANNED FOR USE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|