Plan Review Notes
Plan Review Notes For Permit 01010252
Permit Number 01010252
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-10 00:00:00******************* UNSAT **************
  
 1)NOTEA; PLEASE SUBMITAIC RATING. ALL
 MAINS/PANELS AND EQUIPMENT MUST BEARATED
 FOR THE AVAILABLE FAULT CURRNET PER
 110-9.
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS IN
 DWELLING PER NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE SHOW COLD WATER PIPE ON
 GROUNDING ELECTRODE SYSTEM.
  
 4)NOTE: PLEASE SHOW MEANS OF EGRESS
 LIGHTING REQ`D BY 210-70. EITHER SW
 OUTLET OR LIGHT FIXTURE.
  
 5)NOTE:PLEASE SEE MISSING GFI OUTLET FOR
 A/C COND UNIT. PER 309.2
  
 6)NOTE: NEED TO SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3 MUST
 BE 20A AND #12.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL. PLEASE SEE ATTACHED LETTER FOR A
 IC RATINGS FOR ALL PLANS CONTAINING NEW
 EQUIPMENT.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372