Plan Review Notes For Permit 01010252 |
Permit Number |
01010252 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-10 00:00:00 | ******************* UNSAT ************** | | | | 1)NOTEA; PLEASE SUBMITAIC RATING. ALL | | MAINS/PANELS AND EQUIPMENT MUST BEARATED | | FOR THE AVAILABLE FAULT CURRNET PER | | 110-9. | | | | 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS IN | | DWELLING PER NFPA-72 2-2.1.1.1 | | | | 3)NOTE: PLEASE SHOW COLD WATER PIPE ON | | GROUNDING ELECTRODE SYSTEM. | | | | 4)NOTE: PLEASE SHOW MEANS OF EGRESS | | LIGHTING REQ`D BY 210-70. EITHER SW | | OUTLET OR LIGHT FIXTURE. | | | | 5)NOTE:PLEASE SEE MISSING GFI OUTLET FOR | | A/C COND UNIT. PER 309.2 | | | | 6)NOTE: NEED TO SHOW THE REQ`D DEDICATED | | BATH(S) CIRCUIT(S) PER 210-11-C-3 MUST | | BE 20A AND #12. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | E CALL. PLEASE SEE ATTACHED LETTER FOR A | | IC RATINGS FOR ALL PLANS CONTAINING NEW | | EQUIPMENT. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|