Plan Review Notes
Plan Review Notes For Permit 00121288
Permit Number 00121288
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE DEPARTMENT CONNECTION TO BE
 LOCATED NO FARTHER THAN 150 FEET FROM
 A FIRE HYDRANT.
 2) A SPARE HEAD BOX CONTAINING AT LEAST
 12 SPARE SPRINKLER HEADS AND WRENCH
 ARE TO BE PROVIDED.
 3) FIRE SPRINKLER SYSTEM TO BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910