Plan Review Notes
Plan Review Notes For Permit 00121276
Permit Number 00121276
Review Stop E
Sequence Number 3
Notes
Date Text
2001-06-04 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE SET OF
 PLANS WERE SUBMITTED. THERE NEEDS TO BE
 ONE FOR RECORD AND ONE THAT COMES BACK
 TO CONTRACTOR FOR FIELD COPY
  
 2)NOTE: PLEASE NOTE THAT ALL CHANGES ON
 PLANS NEED TO BE DONE BY THE ARCH/ENG
 OFRECORD PER 471.025 AND 481.221.
 PLEASEHAVE PLANS REPRINTED WITH CHANGES
 AND SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 87372