2001-01-23 00:00:00 | CHECKLIST: |
| 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| BRING STAMPED DRAWINGS AND RECEIPT. |
| 2-REVISE ENERGY CALCULATIONS: |
| -THERE ARE 4 BEDRMS, NOT 3. SEE PLANS. |
| -REVISE A/C AREA AND CEILING AREA AS |
| REQUIRED TO MATCH PLANS. |
| -PROVIDE ORIGINAL SIGNATURES. |
| 3-STORM PANELS: |
| -PROVIDE KEY PLAN AND INSTALLATION |
| SCHEDULE (SEE CITY SAMPLE). |
| -SPECIFY/HIGHLIGHT/CIRCLE SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TO BE |
| USED ACCORDING TO MEAN ROOF HEIGHT, |
| DESIGN PRESSURES, PANEL SPAN, EDGE |
| DISTANCE, CONNECTION TYPE AND |
| STRUCTURE TO BE ATTACHED TO. |
| -DRAWINGS AND PRODUCT APPROVAL REPORT |
| DON'T MATCH. |
| 4-INTERIOR BEARING PARTITION FOOTING TO |
| HAVE 16" MIN. DEPTH AS PER SECTION |
| 1804.1.3 SBC 1997 AND SECTION |
| 1804.1.9 CITY AMENDMENTS TO SBC 1997. |
| 5-SEE COMMENTS ON PLANS. INCLUDING THOSE |
| BY THE OTHER TRADES.AND REVISE/UPDATE. |
| 6-REAR ELEVATION AND FLOOR PLAN DON'T |
| MATCH. SEE COLUMN BET. FRENCH DOORS. |
| 7-TRUSS DRAWINGS: |
| -ENGINEERED TRUSSES TO HAVE ORIGINAL |
| SIGNATURE, DATE AND SEAL. FL. STATUTES |
| -UPDATE GENERAL DETAILS AND SIGN, SEAL |
| AND DATE ACCORDINGLY. 471 FL. STATUTES |
| -TRUSS LAYOUT TO HAVE ENGINEER'S |
| SEAL, DATE AND SIGNATURE ALONG WITH |
| INFORMATION AS REQUIRED BY CHAPTER 471 |
| OF FLORIDA STATUTES. |
| -CLEARLY INDICATE ON ENGINEERED TRUSSES |
| AND TRUSS LAYOUT WHO REVIEWED THEM. |
| -REVISE ROOF CONNECTOR SCHEDULE SHOWING |
| CONNECTORS THAT WILL RESIST THE UPLIFT |
| LOADS CALCULATED IN THE ENGINEERED |
| TRUSSES. SEE COMMENTS ON SHEET 3B. |
| 8-PROVIDE COMPLETE SPECIFICATIONS FOR |
| INTERIOR BEARING WALL: STUD SPACING |
| AND MAXIMUM UNSUPPORTED STUD HEIGHT. |
| DETAIL ON SHEET 3B LACKS THIS INFO. |
| 9-PROVIDE CURRENT SBCCI OR DADE COUNTY |
| PRODUCT APPROVALS FOR: |
| -ENTRY DOOR WITH SIDELITE ASSEMBLY |
| (WITH LEGIBLE DRAWINGS). |
| -GARAGE SIDE DOOR. |
| -WINDOW MULLIONS. |
| -FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY |
| (OR AS SHOWN ON REAR ELEVATION). |
| -SINGLE HUNG WINDOWS. |
| -RECTANGULAR AND ROUND FIXED WINDOWS. |
| 10-PROVIDE SOIL TEST REPORT AS PER SECT. |
| 1804.2.7 AND TABLE 1804.2.7.3 OF CITY |
| AMENDMENTS. (NOT SOUTH FLORIDA BLDG |
| CODE -BROWARD EDITION). |
| 11-SOIL TEST REPORT AS PER SEC 1804.2.7 |
| AND TABLE 1804.2.7.3 CITY AMENDMENTS. |
| NOT SFBC (BROWARD ED.). |
| NOTES: |
| -PLEASE RETURN REVIEWED SET AFTER |
| CORRECTIONS ARE DONE TO THE ORIGINALS |
| IN ORDER TO EXPEDITE THE REVIEW PROCESS |