Plan Review Notes For Permit 00121189 |
Permit Number |
00121189 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE NO | | FARTHER THAN 150 FEET FROM A FIRE | | HYDRANT. | | 2) THE ENTIRE BUILDING IS TO BE | | COMPLETELY FIRE SPRINKLER PROTECTED. | | THIS INCLUDES ALL ELECTRICAL, MECHANICAL | | AND SERVICE ROOMS. ALL VERTICAL SHAFTS | | ARE ALSO TO BE PROPERLY FIRE SPRINKLER | | PROTECTED. | | 3) THE STANDPIPE SYSTEM IS REQUIRED TO | | PROVIDE 750 GPM AT 65 PSI AT THE ROOF. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|