Plan Review Notes
Plan Review Notes For Permit 00121189
Permit Number 00121189
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE DEPARTMENT CONNECTION TO BE NO
 FARTHER THAN 150 FEET FROM A FIRE
 HYDRANT.
 2) THE ENTIRE BUILDING IS TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL ELECTRICAL, MECHANICAL
 AND SERVICE ROOMS. ALL VERTICAL SHAFTS
 ARE ALSO TO BE PROPERLY FIRE SPRINKLER
 PROTECTED.
 3) THE STANDPIPE SYSTEM IS REQUIRED TO
 PROVIDE 750 GPM AT 65 PSI AT THE ROOF.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910