Plan Review Notes
Plan Review Notes For Permit 00121147
Permit Number 00121147
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLANS SHOW A MAIN DISCONNECT
 NEXT TO METERCAN AND RISER SHOWS NO MAIN
 DSIC??? PLEASECORRELATE
  
 2)NOTE: PLEASE NOTE THAT RISER SHOWS 3#1
 CONDUCTORS IN A 8" CONDUIT? PLEASE CORR-
 -ECT OR CLARIFY.
  
 3)NOTE: PLANS SHOW A FAN BEING SWITCHED
 IN BEDROOMS AND NO LIGHT? IS IT A FAN/
 LIGHT? IF SO PLEASE SHOW FANS W/ LT KITS
  
 4)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW THE DISC REQ`D FOR A/C CU. PLEASE
 SHOW PER 440-11
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 CU PER MECH CODE 309.1 AND/OR GFI OUTLET
 MISSING IN REAR OF DWELLING PER 210-52E
 THAT MAY SERVE AS GFI FOR CU.
  
 6)NOTE: PLEASE SHOW OUTLET INFRONT OF
 DWELLING AS GFI PER 210-8
  
 7)NOTE: PLEASE KW FOR ALL ON PANEL SCHED
 -ULE AND SHOW LOAD CACULATIONS PER 215-5
  
 8)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
 MUST BE #12 AND 20A
  
 9)NOTE: PLEASE NOTE MISSING OUTLETS PER
 210-52, 2` OF WALL SPACE.
  
 10)NOTE: PLEASE NOTE THAT LOCATION OF
 SD IN COMMON AREA IS SHOWN TOO CLOSE TO
 KITCHEN. PLEASE CHECK NFPA FOR SD SPAC-
 -ING REQ`MENTS
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372