Plan Review Notes
Plan Review Notes For Permit 00120872
Permit Number 00120872
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT BUILDING.
 3) SMOKE DETECTORS WHEN INSTALLED TO BE
 A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 4) BACKFLOW DEVICE TO BE EQUIPPED WITH
 TAMPER SWITCHES.
 5) FIRE ALARM SYSTEM IS TO BE MONITORED
 BY A UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 6) SYSTEM TO BE COMPLETELY TESTED
 AFTER INSTALLATION WITH FIRE RESCUE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910