Plan Review Notes
Plan Review Notes For Permit 00120715
Permit Number 00120715
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********FAILED**********************
  
 1. STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE
 IS REQUIRED.
  
 2. 2 COPIES OF PRODUCT APPROVALS FROM
 METRO/DADE OR SBCCI WILL BE REQUIRED
 FOR THE FOLLOWING:
 A. FRONT DOOR/ NO SIDELITES PER PLAN
 B. GLASS BLOCK 1 HR. RATED (READABLE
 COPIES)
 3. ENERGY CODE MUST BE ORIGINAL WITH
 ADDRESS ON FORMPER 103.1.2 FEC
 4. SOIL LETTER SIGNED & SEALED.
 5. PG. 2 FOOTING REFERENCES 1994 SBC
 SEC. 1884.13 SHOULD BE 1997 SBC
 SEC. 1804.1.3.HAVE DESIGN
 PROFESSIONAL CORRECT DRAWINGS.
 NOTE:THIS SAME ERROR HAS BEEN
 SUBMITTED ON PREVIOUS PERMIT APPL.
 AND HAS NOT BEEN CORRECTED TO DATE.
 6. VALUE OF HOUSE HAS BEEN ADJUSTED.
 ADD'L PERMIT FEES DUE.
  
 7. NEED NOTICE OF COMMENCEMENT BEFORE
 PICKUP.
  
 ANY QUESTIONS PLEASE CALL LEA SMITH
 AT 659-8096 EXT 8394