2001-02-14 00:00:00 | PROVISO:AS PER NFPA 90A 4-4.4.2, DUCT | | SMOKE DETECTOR SHALL BE TIED WITH | | BUILDING FIRE ALARM, IF BUILING FIRE | | ALARM DOES NOT EXIST, DUCT SMOKE | | DETECTORS SHALL ACTIVATED STROBE/ALARM | | IN OCCUPIED AREAS. | | | | AS PER 97 SMC 609.1.1, NO COMBUSTIBLES | | SHALL BE ABOVE CEILING IN RETURN AIR | | PLENUM. | | | | FIRE DAMPER IS REQUIRED FOR MOTORIZED | | DAMPER INTAKE OPENING FOR AHU 1 AS PER | | 97 610.1.2 (CORRIDOR TO BE PROTECTED | | PER 97SBC 1006.2.2) |
|