2001-02-14 00:00:00PROVISO:AS PER NFPA 90A 4-4.4.2, DUCT
 SMOKE DETECTOR SHALL BE TIED WITH
 BUILDING FIRE ALARM, IF BUILING FIRE
 ALARM DOES NOT EXIST, DUCT SMOKE
 DETECTORS SHALL ACTIVATED STROBE/ALARM
 IN OCCUPIED AREAS.
  
 AS PER 97 SMC 609.1.1, NO COMBUSTIBLES
 SHALL BE ABOVE CEILING IN RETURN AIR
 PLENUM.
  
 FIRE DAMPER IS REQUIRED FOR MOTORIZED
 DAMPER INTAKE OPENING FOR AHU 1 AS PER
 97 610.1.2 (CORRIDOR TO BE PROTECTED
 PER 97SBC 1006.2.2)