2001-01-08 00:00:00PLUMBING PLAN REVIEW,PAUL SCHMITZ
 PROVISO
 (1) SHT A-1 BREAK RM #239 SINK TO COMPLY
 W/ FACBNC 4.24, SHOW ELEVATION DETAIL
 HGTH 34" ABOVE FF, BY 30" WIDE.
 KNEE CLEARANCE 27" HIGH, 30" WIDE,
 19" MAX DEPTH.
 (2) SHT A-1 H/C REST RM'S # 248,253 TO
 COMPLY W/FACBC 4.17.5 DOORS SHALL NOT
 SWING INTO THE CLEAR FLR SPACE OF ANY
 FIXTURE.
 (3) SHT P-1 NOTE (2) & (4) HOT & COLD
 WATER SUPPLY TO BE PROTECTRED WITH A
 RPZV, SPC 94 SEC 606.
 (4) SHT P-1 NOTE 16, AIR CHAMBERS TO
 COMPLY WITH SPC 94 SEC 607.8.3 TO BE
 READLY ACCESSIBLE AND RECHARGEABLE.
 END OF COMMENTS
  
  
 CHANGED TO PROVISO PER BILL STAPLES