Plan Review Notes For Permit 00120664 |
Permit Number |
00120664 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | SHOULD READ NFPA 101, 1985 EDITION | | INSTEAD OF 1998 EDITION. | | 2) CODE COMPLIANCE NOTE # 7 INDICATES | | NO FIRE SUPPRESSION SYSTEM IS PLANNED. | | AUTOMATIC FIRE SUPPRESSION IS REQUIRED | | FOR THE BUILDING. PLEASE PROVIDE | | FIRE SUPPRESSION INFORMATION ON THE | | NEXT PLAN SUBMITTAL. | | 3) ADDITIONAL EMERGENCY LIGHTING | | EQUIPMENT APPEARS TO BE NEEDED IN THE | | SPACE. | | 4) IT APPEARS THAT ADDITIONAL EXIT SIGNS | | ARE NEEDED TO DIRECT PERSONS TO THE | | EAST EXIT STAIRS. | | 5) ADDITIONAL EMERGENCY LIGHTING APPEARS | | TO BE NEEDED IN CORRIDOR 209 EAST. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|