2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ NFPA 101, 1985 EDITION
 INSTEAD OF 1998 EDITION.
 2) CODE COMPLIANCE NOTE # 7 INDICATES
 NO FIRE SUPPRESSION SYSTEM IS PLANNED.
 AUTOMATIC FIRE SUPPRESSION IS REQUIRED
 FOR THE BUILDING. PLEASE PROVIDE
 FIRE SUPPRESSION INFORMATION ON THE
 NEXT PLAN SUBMITTAL.
 3) ADDITIONAL EMERGENCY LIGHTING
 EQUIPMENT APPEARS TO BE NEEDED IN THE
 SPACE.
 4) IT APPEARS THAT ADDITIONAL EXIT SIGNS
 ARE NEEDED TO DIRECT PERSONS TO THE
 EAST EXIT STAIRS.
 5) ADDITIONAL EMERGENCY LIGHTING APPEARS
 TO BE NEEDED IN CORRIDOR 209 EAST.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497