Plan Review Notes For Permit 00120631 |
Permit Number |
00120631 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) SMOKE DETECTOR REQUIRED ABOVE FIRE | | ALARM CONTROL PANEL. | | 2) NO FLOWS OR TAMPER SWITCHES SHOWN. | | THE BUILDING IS FIRE SPRINKLER PROTECTED | | 3) SYSTEM TO BE CLASS A, STYLE D WIRED. | | 4) FIRE ALARM SYSTEM TO BE MONITORED BY | | A LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 5) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | TO BE AUDIBLE THROUGHOUT BUILDING. | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|