2001-03-13 00:00:00PLANS ARE APPROVED PROVISO WITH THE
 FOLLOWING CONDITIONS:
  
 1) THE NITROGEN PAD AND PIPING PLANNED
 FOR THE EXTERIOR OF THE BUILDING WILL
 BE UNDER SEPARATE PLANS AND PERMIT.
 2) THE FLAMMABLE GAS STORAGE AND PIPING
 PLANNED FOR THE BUILDING WILL BE UNDER
 SEPARATE PLANS AND PERMIT.
 3) MORE DETAILS NEEDED ON THE FUME HOOD.
 4) THE ROOMS WHERE THE FLAMMABLE GAS
 WILL BE STORED, MUST BE AT LEAST TWO
 HOUR RATED, HAVE PROPER VENTILATION,
 EXPLOSION PROOF FIXTURES, APPROPRIATE
 SIGNAGE, AND DOORS.
  
 CAPTAIN MIKE CARSILLO