2001-04-27 00:00:00 | REVISION : 4/20/01 |
| BUILDING PLAN REVIEW |
| |
| 1)- AS PART OF THE PROVISO THIS AREA |
| WAS THE SECOND OF (2) AREAS NOT COVERED |
| UNDER THE INTERIOR BUILD OUT PERMIT. |
| THIS AREA WOULD REQUIRE A SEPERATE |
| PERMIT AND FEES. SEE THE ORIGINAL PRO- |
| VISO ATTACHED TO THE STAMPED PLANS. |
| |
| 2)- DESCRIPENCY: THE MINOR AMENDMENT |
| DECLAIRS THAT A NITROGEN TANK IS TO BE |
| INSTALLED WHEREAS THE PLANS DEPICTS A |
| OXYGEN TANK? IF OXYGEN, IS THIS COMPRESS |
| ED OXYGEN OR REFRIGARATED LIQUID OXYGEN |
| |
| 3)- THE PLANS ARE NOT CLEAR AS TO THE |
| SIZE OF THE TANK?TYPE OF TANK? OR |
| HOW THE TANK WILL BE FASTENED TO THE |
| SLAB TO RESIST OVERTURNING IN A HURRI- |
| CANE? IS THERE A FASTY FACTOR FIGURED IN |
| TO THIS FORMULA? THE PIPING AND SAFETY |
| VALVES ARE TO BE UNDER A MED-GAS PERMIT. |
| |
| 4)- THIS AREA IS NEXT TO A PROPOSED |
| SCREENED IN COVER, WHAT IS THIS AREA TO |
| BE USED FOR? IF THE TANK IS COMPRESSED |
| NITROGEN WHAT SAFETY FEATURES ARE TO |
| BE CONSIDERED FOR GAS LEAKS, THE CONCERN |
| SIMPLE ASPHYXIATION. |
| |
| 5)- NO INFORMATION ON WARNING SIGNS NOR |
| LABELS IDENTIFYING THE TYPE OF HAZARD OR |
| TYPE OF MATERIAL. |
| |
| 6)- THE INTERIOR BUILDOUT HAD THESE |
| DOORS AS EXIT DOORS, SHOW THE PATH OF |
| TRAVEL, TYPE OF MATERIALS THIS COVER |
| WILL BE MADE OF, WALLS & ROOF? |
| |
| 8)- A SITE PLAN WILL BE REQUIRED TO SHOW |
| THE RELAVENCE TO THE PROJECT AS A WHOLE. |
| |
| 9)- THE SCREEN ENCLOSURE AND ASSUMED |
| METAL ROOF WILL REQUIRE A SEPERATE |
| PERMIT, WILL THIS ROOF HAVE A FOAM INSUL |
| ATION CORE? METAL STRUCTURES ALSO |
| REQUIRES ENGINEERING, SIGNED SEALED & |
| DATED. |
| |
| 10)- IF THE TANK DEPICTED IS TO BE |
| OXYGEN CHECK MSDS SHEETS FOR THE CLOSE- |
| NESS TO FLAMMABLES OR THE BARRICADE OF |
| NON-COMBUSTIBLES. |
| |