2001-04-27 00:00:00REVISION : 4/20/01
 BUILDING PLAN REVIEW
  
 1)- AS PART OF THE PROVISO THIS AREA
 WAS THE SECOND OF (2) AREAS NOT COVERED
 UNDER THE INTERIOR BUILD OUT PERMIT.
 THIS AREA WOULD REQUIRE A SEPERATE
 PERMIT AND FEES. SEE THE ORIGINAL PRO-
 VISO ATTACHED TO THE STAMPED PLANS.
  
 2)- DESCRIPENCY: THE MINOR AMENDMENT
 DECLAIRS THAT A NITROGEN TANK IS TO BE
 INSTALLED WHEREAS THE PLANS DEPICTS A
 OXYGEN TANK? IF OXYGEN, IS THIS COMPRESS
 ED OXYGEN OR REFRIGARATED LIQUID OXYGEN
  
 3)- THE PLANS ARE NOT CLEAR AS TO THE
 SIZE OF THE TANK?TYPE OF TANK? OR
 HOW THE TANK WILL BE FASTENED TO THE
 SLAB TO RESIST OVERTURNING IN A HURRI-
 CANE? IS THERE A FASTY FACTOR FIGURED IN
 TO THIS FORMULA? THE PIPING AND SAFETY
 VALVES ARE TO BE UNDER A MED-GAS PERMIT.
  
 4)- THIS AREA IS NEXT TO A PROPOSED
 SCREENED IN COVER, WHAT IS THIS AREA TO
 BE USED FOR? IF THE TANK IS COMPRESSED
 NITROGEN WHAT SAFETY FEATURES ARE TO
 BE CONSIDERED FOR GAS LEAKS, THE CONCERN
 SIMPLE ASPHYXIATION.
  
 5)- NO INFORMATION ON WARNING SIGNS NOR
 LABELS IDENTIFYING THE TYPE OF HAZARD OR
 TYPE OF MATERIAL.
  
 6)- THE INTERIOR BUILDOUT HAD THESE
 DOORS AS EXIT DOORS, SHOW THE PATH OF
 TRAVEL, TYPE OF MATERIALS THIS COVER
 WILL BE MADE OF, WALLS & ROOF?
  
 8)- A SITE PLAN WILL BE REQUIRED TO SHOW
 THE RELAVENCE TO THE PROJECT AS A WHOLE.
  
 9)- THE SCREEN ENCLOSURE AND ASSUMED
 METAL ROOF WILL REQUIRE A SEPERATE
 PERMIT, WILL THIS ROOF HAVE A FOAM INSUL
 ATION CORE? METAL STRUCTURES ALSO
 REQUIRES ENGINEERING, SIGNED SEALED &
 DATED.
  
 10)- IF THE TANK DEPICTED IS TO BE
 OXYGEN CHECK MSDS SHEETS FOR THE CLOSE-
 NESS TO FLAMMABLES OR THE BARRICADE OF
 NON-COMBUSTIBLES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412