2001-03-13 00:00:00 | PROVISO: 3/13/01 AS OF A MEETING TODAY |
| WITH NANCY DENMARK, MIKE CARLSELO, JIM |
| WITMER THE CONTRACTOR MARK BUTTERS AND |
| FRANK BUTTERS WE ARE IN AGGREEMENT TO |
| ISSUE THTE BUILDING PERMIT WITH A PRO- |
| VISO AND ADDITIONAL INFORMATION TO BE |
| SUBMITTED THROUGH SUBPERMITS. AREAS NOT |
| TO BE COVERED UNDER THIS PERMIT WILL BE |
| THE OUTFITTING OF ROOMS103,103A,107,& |
| 107A. THE CONTRACTOR MAY FORM AND POUR |
| THE WALLS & CEILING OF THESE ROOMS. |
| THE SECOND AREA NOT INCLUDED UNDER THIS |
| PERMIT WILL BE THE 550 SQ. FT DECK ON |
| THE EXTERIOR OF THE BUILDING AS WELL AS |
| THE SLAB ENCLOSURE AND 500 GAL. NITROGEN |
| TANK TO BE LOCATED ON THE SOUTH SIDE OF |
| THE BUILDING. |
| |
| PROVISO: |
| 1)- THE CONTTRACTOR WILL SUPPLY ALL THE |
| EQUIRED INFORMATION REQUIRED TO MEET |
| THE REQUIREMENTS OF SBC 407.2 1-10. |
| |
| 2)- THE ARCHITECT WILL REVISE THE WALLS |
| FOR THE CLOSET THAT WILL HOUSE THE |
| HYDROGEN AS PERNFPA 50A .4.3.1 OPENINGS |
| TO OTHER PARTS OF THE BUILDING SHALL NOT |
| BE PERMITTED. |
| |
| 3)- NFPA 50A WILL BE FOLLOWED FOR THE |
| USE OF HYDROGEN IN SPECIAL ROOMS. |
| |
| 4)-NFPA 55 WILL BE FOLLOWED FOR THE |
| USE OF LIQUID GASES IN PORTABLE CYLINDER |
| |
| 5)- THE ARCHETECT WILL CORRECT THE FLOOR |
| DRAIN SHOWN IN THE ISOMETRIC FOR THE |
| CONTANMENT ROOM. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |