2001-01-08 00:00:00**********DENIED************************
 1. PROVIDE INFORMATION ON CHEMICALS
 USED IN LABS.DO EXHAUST FAN MOTORS NEED
 TO BE PROTECTED (EXPLOSION PROOF)?
 2. DOES THE M.S.D.S. REQUIRE ADDITIONAL
 VENTILATION.
 3. IS THERE ANY LAB PIPING? IF SO
 PROVIDE COMPLIANCE WITH NFPA 99C.
 4.DO NOT ALLOW RECIRCULATION OF
 CONTAMINATED AIR. MINIMUM OF 10 FEET
 REQUIRED BETWEEN EXHAUST OUTLETS AND
 INTAKE OPENINGS.