2001-01-08 00:00:00BUILDING PLAN RREVIEW
 WECAN'T DO A COMPETANTAND THOUROUGH
 REVIEW OF THE PLANS WITH OUT ADDITIONAL
 INFORMATION, WE WILL REQUIRE AMSDA
 LISTINGS SHEET, (MATERIALS SAFETY DATA
 SHEET) OF ALL HAZARDOUS MATERIALS WITH
 TYPE OF HAZARD GROUP/ CLASS, QUANITY,
 IF LIQUID, SOLID OR GAS.
 1).WHAT TYPE OF BUSINESS IS THIS, THERE
 IS CLASSROOMS,LABS ETC, IS THIS EDUCA-
 TIONAL?
 2). ROOM #159 ITS- WHAT IS THIS ROOM TO
 BE USED FOR?
 3). ROOM #155 CONTAINMENT ROOM- WHAT
 TYPE OF MATERIALS ARE TO BE STOED IN
 THIS ROOM? IS THERE GOING TO BE MORE
 THAN THE (2) 55 GAL DRUMS?
 4).R00M #154 STORAGE, IS THERE GOING TO
 HAVE ANY TYPE OF HAZARDOUS STORAGE THERE
 5).CLOSETS 103,103A, 107 & A07A SHOW
 THAT THEY ARE TO BE CONTROLED AREAS
 CONTAINING HAZARDOUS MATERIALS NOT EX-
 CEEDINGTHE EXEMPT QUANITIES,WHAT TYPE
 OF MATERIALS ARE TO BE STORED IN THESE
 AREAS/ QUANITITIES?
 CLOSETS 103,103A,107, 107A & 155 ARE TO
 COMPLY WITH S.B.C. 308.2.2 WITH 3/4HR
 OPENING PROTECTION WITH SELF CLOSING OR
 AUTOMATIC CLOSING DEVISE IN ACCORDANCE
 WITH 705.1.3.2.3.
 6). S.B.C.407.1.3.5-LABORATORY FUME HOOD
 WHERE FLAMMABLE MATERIALS ARE TO BE USED
 SHALL BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM.
 7). DEPENDING ON THE AMOUNTS OF HAZARD-
 OUS MATERIALS STORED, THESE CODE SECTION
 MAY BE APPLICABLE:
 S.B.C. 407.2.3.1 SPILL CONTROL, DRAINAGE
 AND CONTAINMENT.
 S.B.C. 407.2.3.3 DRAINAGE
 S.B.C. 407.2.3.4 SECONDARY CONTAINMENT
 VENTILATION, ALARMS , DETECTION &
 FIRE SPRINKLER SYSTEM.
  
 BUILDING REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412