2001-01-08 00:00:00 | BUILDING PLAN RREVIEW |
| WECAN'T DO A COMPETANTAND THOUROUGH |
| REVIEW OF THE PLANS WITH OUT ADDITIONAL |
| INFORMATION, WE WILL REQUIRE AMSDA |
| LISTINGS SHEET, (MATERIALS SAFETY DATA |
| SHEET) OF ALL HAZARDOUS MATERIALS WITH |
| TYPE OF HAZARD GROUP/ CLASS, QUANITY, |
| IF LIQUID, SOLID OR GAS. |
| 1).WHAT TYPE OF BUSINESS IS THIS, THERE |
| IS CLASSROOMS,LABS ETC, IS THIS EDUCA- |
| TIONAL? |
| 2). ROOM #159 ITS- WHAT IS THIS ROOM TO |
| BE USED FOR? |
| 3). ROOM #155 CONTAINMENT ROOM- WHAT |
| TYPE OF MATERIALS ARE TO BE STOED IN |
| THIS ROOM? IS THERE GOING TO BE MORE |
| THAN THE (2) 55 GAL DRUMS? |
| 4).R00M #154 STORAGE, IS THERE GOING TO |
| HAVE ANY TYPE OF HAZARDOUS STORAGE THERE |
| 5).CLOSETS 103,103A, 107 & A07A SHOW |
| THAT THEY ARE TO BE CONTROLED AREAS |
| CONTAINING HAZARDOUS MATERIALS NOT EX- |
| CEEDINGTHE EXEMPT QUANITIES,WHAT TYPE |
| OF MATERIALS ARE TO BE STORED IN THESE |
| AREAS/ QUANITITIES? |
| CLOSETS 103,103A,107, 107A & 155 ARE TO |
| COMPLY WITH S.B.C. 308.2.2 WITH 3/4HR |
| OPENING PROTECTION WITH SELF CLOSING OR |
| AUTOMATIC CLOSING DEVISE IN ACCORDANCE |
| WITH 705.1.3.2.3. |
| 6). S.B.C.407.1.3.5-LABORATORY FUME HOOD |
| WHERE FLAMMABLE MATERIALS ARE TO BE USED |
| SHALL BE PROTECTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM. |
| 7). DEPENDING ON THE AMOUNTS OF HAZARD- |
| OUS MATERIALS STORED, THESE CODE SECTION |
| MAY BE APPLICABLE: |
| S.B.C. 407.2.3.1 SPILL CONTROL, DRAINAGE |
| AND CONTAINMENT. |
| S.B.C. 407.2.3.3 DRAINAGE |
| S.B.C. 407.2.3.4 SECONDARY CONTAINMENT |
| VENTILATION, ALARMS , DETECTION & |
| FIRE SPRINKLER SYSTEM. |
| |
| BUILDING REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412 |