Plan Review Notes
Plan Review Notes For Permit 00120494
Permit Number 00120494
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 TO INCLUDE ALL NEW POOL EQUIPMENT.
  
 2)NOTE: PLEASE SHOW SIZE OF EXISTING
 SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved