Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SEE 210-8-A-6 AND SHOW
 ALL OUTLETS SERVING KITCHEN COUNTER-
 SPACE AS GFI/ GFI PROTECTED.
  
 2)NOTE: PLEASE NOTE THAT NO SECOND FLOOR
 ELECTRICAL WAS SUBMITTED FOR CARRIAGE
 HOUSE.??
  
 3)NOTE: PLEASE SEE 210-8 FOR GARAGE
 GFI PROTECTION.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 AND SHOW RISER DIAGRAM TO SHOW EXISTING
 SERVICE EQUIPMENT SIZES. PLAN SHOWING
 NEW POOL/ A/C EQUIPMENT. PLEASE SUBMIT
 NEW PANEL SCHEDULES.
  
 5)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR A/C EQUIPMENT. PER MECH CODE 300.9
  
 6)NOTE:PLEASE SEE LOCATION OF OUTLET
 SERVING BATH IN CARR. HOUSE. PER 210-52D
 AND SEE 210-11-C-3 FOR REQ`MNETS OF
 CIRCUIT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372