Plan Review Notes For Permit 00111365 |
Permit Number |
00111365 |
|
Review Stop |
P |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2001-09-22 00:00:00 | REVISION DENIED; | | 1.SANITARY RISER DIAGRAM S-2 NOT SIZED | | PROPERLY. AT 1/4" PER FOOT MAX. | | FIXTURE UNITS IS 27. YOU SHOW 31 FU'S. | | 2.PAGE P-2 URINAL MISS MARKED SHOULD BE | | P-4 NOT P-7. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 | | 3.PAGE P-2 DOOR FROM MENS BATHROOM TO | | MENS LOUNGE MUST SWING OUT NOT IN, | | MARKED IN RED ON APPROVED DRAWINGS. | | DRAWINGS APPROVED ON JULY 25,2001. |
|