Plan Review Notes
Plan Review Notes For Permit 00111365
Permit Number 00111365
Review Stop P
Sequence Number 3
Notes
Date Text
2001-06-10 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT 1.2, MEN'S LOCKER RM, ENTERANCE
 DOOR,SWINGS INTO STALL DOOR,SEC 4.22
 (2) SHT 3.4, DETAIL 9,12 RE: GRAB BAR
 LENGTH,CONFLICTS WITH DETAIL ON SHT 3.8
 COMPLY W/FACBC 97 FIG.30 PG.108
 (3) SHT P-1, WATER SERVICE, BACK FLOW
 PREVENTER REQ.SPC 94 SEC 606.
 (4) SHT P-5 DOMESTIC WATER RISER,PIPE
 SIZES, NO MORE THAN 2 FIXTURES ON 1/2"
 COLD WATER, NO MORE THAN 4 FIXTURES ON
 1/2' HOT WATER.SPC 94 CNTY. W/AMENDMENTS
 (5) SHT P-5, PLUMBING SPECIFICATIONS
 MATRIALS, NOTE (F) AIR CHAMBERS TO BE
 RECHARGEABLE & ACCESSIBLE.
 SPC 94 SEC 607.8.3
 END OF COMMENTSPAUL SCHMITZ